Major Components

5

3.0

M

AJOR

C

OMPONENTS

3.1

T

RANSIENT

V

OLTAGE

S

URGE

S

UPPRESSION

(TVSS)

AND

EMI/RFI F

ILTERS

These UPS components provide surge protection and filter both elec-

tromagnetic interference (EMI) and radio frequency interference

(RFI). They minimize any surges or interference present in the utility

line and keep the sensitive equipment protected.

3.2

R

ECTIFIER

/P

OWER

F

ACTOR

C

ORRECTION

(PFC) C

IRCUIT

In normal operation, the rectifier/power factor correction (PFC) circuit

converts utility AC power to regulated DC power for use by the

inverter while ensuring that the waveshape of the input current used

by the UPS is near ideal. Extracting this sinewave input current

achieves two objectives:

• The utility power is used as efficiently as possible by the UPS.
• The amount of distortion reflected on the utility is reduced.

This results in cleaner power being available to other devices in the

building not being protected by the UPStation GXT 2U.

3.3

I

NVERTER

In normal operation, the inverter utilizes the DC output of the power

factor correction circuit and inverts it into precise, regulated sinewave

AC power. Upon a utility power failure, the inverter receives its

required energy from the battery through the DC to DC converter. In

both modes of operation, the UPS inverter is on-line and continuously

generating clean, precise, regulated AC output power.

Input

Output

Inverter

Battery

Battery

Charger

DC to DC

Converter

Rectifier

/PFC

TVSS &

EMI/RFI

Filters

L1

L2

G

L1

L2

G

Dynamic

Bypass

Advertising