Troubleshooting

30

Fault and Bypass

indicator LEDs

and diagnostic

LED C and E are

illuminated.

UPS shutdown due to a

command from the

communications port(s).

Your UPS has received a

signal or command from

the attached computer. If

this was inadvertent,

ensure the communication

cable used is correct for

your system. For

assistance, contact your

local dealer, Liebert

representative or the

Liebert Worldwide Support

Group.

AC LED is

flashing.

UPS detected a line-to-

neutral reversal or a loss of

proper grounding;

continuous horn and UPS

will not start.This is active

only when power is first

applied to the input. Once

the UPS is running, the AC

LED will not start flashing,

even if the input wiring is

changed.

Contact a qualified

electrician to verify site

wiring.

Battery LED is

flashing.

Battery source is not

available; continuous horn.

Check battery connections,

completely power down

and restart UPS.

NOTE: If the battery circuit

opens while the UPS is

running, it will be detected

when the next battery test

is performed.

Bypass LED is

flashing.

Bypass voltage is present,

but is disabled for use

because the voltage or

frequency is outside

acceptable limits.

The AC input powers the

PFC input and serves as

the bypass source. If the

AC is present but the

voltage or frequency

exceeds the acceptable

range for safe operation

with a load, the bypass will

be disabled and this LED

will flash, indicating that the

bypass is unavailable.

Table 1

Troubleshooting guide (continued)

Problem

Cause

Solution