Refrigerant piping, Caution, Permissible piping length and head – Toshiba RAM-SM560BT-E User Manual

Page 101

Advertising
background image

98

B

6

REFRIGERANT PIPING

Refrigerant Piping

1. If the outdoor units are to be mounted on a wall, make sure that the platform supporting is sufficiently strong.

The platform should be designed and manufactured to maintain its strength over a long period of time, and
sufficient consideration should be given to ensuring that the outdoor unit will not fall.

2. Use copper pipe with 0.8 mm or more thickness.

3. Flare nut and flare works are also different from those of the conventional refrigerant.

Take out the flare nut attached to the main unit of the air conditioner, and use it.

CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

1. Take away dust and moisture from the inside of the connecting pipes.

2. Tight connection (between pipes and unit)

3. Evacuate the air in the connecting pipes using VACUUM PUMP.

4. Check the gas leakage. (Connected points)

Permissible Piping Length and Head

Imperial (Wing nut type)

• Flaring dia meter size : A (Unit : mm)

*

In the case of flaring for R410A with the conventional
flare tool, pull out it approx. 0.5 mm more than that for
R22 to adjust to the specified flare size.

The copper pipe gauge is useful
for adjusting projection margin size.

+0
- 0.4

A

Flaring

Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R410A differ from those of refrigerant R22, the flare
tools newly manufactured for R410A are recommended.

However, the conventional tools can be used by adjusting projection margin
of the copper pipe.

• Projection margin in flaring : B (Unit : mm)

Rigid (Clutch type)

Outer diam. of

copper pipe

6.35

9.52

12.7

R410A tool used

R410A

R22

0 to 0.5 (Same as left)

0 to 0.5 (Same as left)

0 to 0.5 (Same as left)

Conventional tool used

R410A

R22

1.0 to 1.5

0.5 to 1.0

1.0 to 1.5

0.5 to 1.0

1.0 to 1.5

0.5 to 1.0

Outer diam. of copper pipe

6.35

9.52

12.7

R410A

R22

1.5 to 2.0

1.0 to 1.5

1.5 to 2.0

1.0 to 1.5

2.0 to 2.5

1.5 to 2.0

Outer diam. of copper pipe

6.35

9.52

12.7

A

R410A

R22

9.1

9.0

13.2

13.0

16.6

16.2

The maximum piping length from the outdoor to indoor unit

30 m (Without charge 20m)

50 m (Without charge 20m)

(RAV-SM560AT-E)

(RAV-SM800AT-E)

The maximum height difference outdoor/indoor unit

Outdoor unit is above

Outdoor unit is below

30m

15m