Evacuating – Toshiba RAM-SM560BT-E User Manual

Page 79

Advertising
background image

76

7

EVACUATING

Hexagonal wrench is required.

Compound
pressure gauge Pressure gauge

Manifold valve

Handle Hi
(Keep fully closed)

Charge hose

Vacuum pump
adapter for
counter-flow
prevention

Packed valve at gas side

Service port
(Valve core (Setting pin))

Handle Lo

Charge hose

–101kPa

(–76cmHg)

Vacuum
pump

Packed valve
at liquid side

AIR PURGE

Evacuate the air in the connecting pipes and in the
indoor unit using vacuum pump.
Do not use the refrigerant in the outdoor unit.
For details, see the manual of vacuum pump.

Use a vacuum pump

Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops.

1. Connect the charge hose from the manifold valve

to the service port of the gas side packed valve.

2. Connect the charge hose to the port of vacuum

pump.

3. Open fully the low pressure side handle of the

gauge manifold valve.

4. Operate the vacuum pump to start evacuating.

Perform evacuating for about 35 minutes if the
piping length is 30 meters total for model SM560
and 50 meters for model SM800
(assuming a pump capacity of 27 liters per minute.)
Then confirm that the compound pressure gauge
reading is –101 kPa ( –76 cmHg).

5. Close the low pressure side valve handle of gauge

manifold.

6. Open fully the valve stem of the packed valves

(both sides of Gas and Liquid).

7. Remove the charging hose from the service port.

8. Securely tighten the caps on the packed valves.

Packed valve handling precautions

• Open the valve stem all the way out ; do not try to

open it beyond the stopper.

• Securely tighten the valve stem cap at the torque as

follows:

15.9 mm (diam.)

12.7 mm (diam.)

9.52 mm (diam.)

6.35 mm (diam.)

63 to 77 N•m (6.3 to 7.7 kgf•m)

50 to 62 N•m (5.0 to 6.2 kgf•m)

33 to 42 N•m (3.3 to 4.2 kgf•m)

14 to 18 N•m (1.4 to 1.8 kgf•m)

<For RAV-SM800AT-E model>

• As shown in the figure, be sure to use a double

spanner to loosen or tighten the flare nut of the valve
at gas side. If using a single spanner, the nut cannot
be tightened with necessary tightening torque.

On the contrary, use a single spanner to loosen or
tighten the flare nut of the valve at liquid side.

SM800 type valve at gas side

Cover

Cap

Piping valve

Tightened

Flare nut

Loosened

Cover

Do not put the spanner or
torque wrench, etc. on
the cover.

The valve may be broken.