For rav-sm800at-e model, Packed valve handling precautions – Toshiba RAM-SM560BT-E User Manual

Page 103

Advertising
background image

100

<For RAV-SM800AT-E model>

• As shown in the figure, be sure to use a double

spanner to loosen or tighten the flare nut of the valve
at gas side. If using a single spanner, the nut cannot
be tightened with necessary tightening torque.

On the contrary, use a single spanner to loosen or
tighten the flare nut of the valve at liquid side.

SM800 type valve at gas side

Cover

Cap

Piping valve

Tightened

Flare nut

Loosened

Cover

Do not put the spanner or
torque wrench, etc. on
the cover.

The valve may be broken.

<For RAV-SM560AT-E model>

<For RAV-SM800AT-E model>

Hexagonal wrench is required.

Gas side (12.7 mm (diam.))

Gas side (9.52 mm (diam.))

Liquid side (6.35 mm (diam.))

Service port

50 to 62 N•m (5.0 to 6.2 kgf•m)

33 to 42 N•m (3.3 to 4.2 kgf•m)

14 to 18 N•m (1.4 to 1.8 kgf•m)

14 to 18 N•m (1.4 to 1.8 kgf•m)

Packed valve handling precautions

• Open the valve stem all the way out ; do not try to

open it beyond the stopper.

• Securely tighten the valve stem cap in torque as

follows:

Compound pressure gauge

Service port (Valve core (Setting pin))

Packed valve (Gas side)

Pressure gauge

Manifold valve

Handle Hi
(Keep fully closed)

Charge hose
(For R410A only)

Vacuum pump adapter
for counter-flow prevention
(For R410A only)

Handle Lo

Charge hose
(For R410A only)

–101kPa

(–76cmHg)

Vacuum

pump

Valve rod

Valve unit

Flare nut

Stopper

Charge port

Charge cap

Service port
(Valve core (Setting pin))

Compound pressure gauge

Packed valve at gas side

Pressure gauge

Manifold valve

Handle Hi
(Keep fully closed)

Charge hose
(For R410A only)

Vacuum pump adapter
for counter-flow prevention
(For R410A only)

Handle Lo

Charge hose
(For R410A only)

–101kPa

(–76cmHg)

Vacuum

pump

Advertising
This manual is related to the following products: