Caution, Optional installation parts (local procure), Refrigerant piping connection – Toshiba RAM-SM560BT-E User Manual

Page 9

Advertising
background image

6

Waterproof rubber cap

Base plate

Drain nipple

Knockout hole

Waterproof rubber cap

Open

Drain nipple

<SM560AT-E>

<SM800AT-E>

• When there is a possibility of freezing of drain at the

cold district or a snowfall area, be careful for drainage
ability of drain. The drainage ability increases when a
knockout hole on the base plate is opened. (Open the
knockout hole to outside using a screwdriver, etc.)

Optional Installation Parts
(Local Procure)

A

B

C

Parts name

Refrigerant piping
Liquid side : Ø6.35 mm or Ø9.52 mm
Gas side : Ø12.7 mm or Ø15.9 mm

Pipe insulating material
(polyethylene foam, 6 mm thick)

Putty, PVC tapes

Q’ty

Each one

1

Each one

Refrigerant Piping Connection

CAUTION

TAKE NOTICE THESE IMPORTANT
4 POINTS BELOW FOR PIPING WORK

1. Keep dust and moisture away from inside the

connecting pipes.

2. Tightly connect the connection between pipes

and the unit.

3. Evacuate the air in the connecting pipes using

VACUUM PUMP.

4. Check gas leak at connected points.

<Piping connection>

Capacity

rank

RAV-

SM560

SM800

Liquid side

Outer

Thickness

diameter

Ш6.4

0.8

Ш9.5

0.8

Gas side

Outer

Thickness

diameter

Ш12.7

0.8

Ш15.9

1.0