Additional refrigerant

1. The amount of refrigerant put into the outdoor unit

at the factory is sufficient to fill up to 20m of
refrigerant piping work.

2. If the length of the refrigerant piping work is 20m or

less, addition of refrigerant at the installation site is
unnecessary.

3. If the length of the piping work exceeds 20m, extra

refrigerant must be added. Refer to the outdoor
installation manual for details of the extra amounts.

4. Overcharge or undercharge of refrigerant in the

outdoor unit may cause malfunction of the
compressor.

Add Only R410A Refrigerant to These Units

Heat insulation

1. Provide heat insulation on the refrigerant piping on

both the liquid side and gas side separately, and
ensure that all joints in the insulation are compleatly
sealed (without gap).

2. Since the temperature of the piping on the gas side

increases during heating operations, the heat
insulating material used must be able to withstand
temperatures of more than 120°C.

3. Use the pipe insulation supplied in the accessory

pack to insulate the piping connecting section on
the indoor unit side.

Opened fully

Handle

Closed completely

Valve unit

Valve unit

Charge port

Charge port

Handle
Pull out the handle and
using cutting pliers, etc.
turn it counterclockwise
by 90˚. (Open fully)

Flare nut

Flare nut

Push in handle.

Handle position

*

1. Use the vacuum pump, vacuum pump adapters,

and gauge manifold referring to the manuals
attached to each tool before using them. For the
vacuum pump, check oil is filled up to the specified
line of the oil gauge.

*

2. While the air is purged, check again that the

connecting port of charge hose, which has a
projection to push the valve core, is firmly con-
nected to the charge port.

Valve handling precautions

• Open the valve stem or the handle until it strikes

the stopper. It is unnecessary to apply further
force.

• Securely tighten the cap with a torque wrench.

• Cap tightening torque

Ø6.4

Valve

Ø9.5

size

Ш12.7

Ш15.9

Charge port

14 to 18N•m (1.4 to 1.8kgf•m)

33 to 42N•m (3.3 to 4.2kgf•m)

33 to 42N•m (3.3 to 4.2kgf•m)

20 to 25N•m (2.0 to 2.5kgf•m)

14 to 18N•m (1.4 to 1.8kgf•m)

7

EVACUATING