FILE NO. SVM-03008

– 24 –

8-1-4. Prevent-freezing control

The indoor heat exchanger sensor detects refrigerant
vapor temperature in COOL/DRY operation. If the
temperature is below the specified value, compressor
motor speed is reduced so that operation is performed
in temperature below the specified value to prevent-
freezing of indoor heat exchanger.

8-1-5. P.M.V. (Pulse Modulating Valve)
Using P.M.V., refrigerant flow of refrigeration cycle is
varied for the optimum temperature.

After the power has been turned on, when a serial
operation signal is received from indoor at the first
time, or when PMV alarm is detected and the equip-
ment is reactivated, move the valve once until it hits on
the stopper for positioning of the valve. In this case,
ticktack sound may be heard.

8-1-6. Louver control

(1) Vertical air flow louvers

Positions of vertical air flow louvers are
automatically controlled according to the operation
status (AUTO (A), COOL ( ), DRY ( ), HEAT( )
and FAN ONLY ( ). Besides, positions of vertical
air flow louvers can be arbitrarily set by pushing
the [FIX] button.

(2) Swing

If the [SWING] button is pressed during running
operation, vertical air flow louvers start swinging.
When the [FIX] button is pushed, swinging stops.

LOW

+

=

MED

+

=

LOW+MED

2

MED+HIGH

2

8-1.7. Indoor fan control (DC fan motor)

(1) The indoor fan is operated by the stepless speed

change DC motor.

(2) For air flow level, speed of the indoor fan motor is

controlled in five steps (LOW, LOW

+

, MED, MED

+

and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.

Table 8-1-2

RAS-13UKV-E2

Motor speed Air flow rate

(rpm)

(m

3

/h)

H

1210

530

COOL

M

1010

420

L

810

330

DRY

780

320

H

1290

620

HEAT

M

1110

470

L

930

380

Operation

mode

Fan

mode