Toshiba RAS-13UAV-E2 User Manual

Page 26

Advertising
background image

FILE NO. SVM-03008

– 25 –

8-1-8. Outdoor fan control (DC fan motor)

Although the outdoor fan motor drives the outdoor fan by non-step variable system of the revolution speed, the
revolution speed is restricted to three steps on the convenience of controlling. If a strong wind is lashing outside
of the room, the operation may be continued as the outdoor fan stops in order to protect the outdoor fan motor.

If a fan lock occurred due to entering of foreign matter, the air conditioner stops and an alarm is displayed.

<COOL, DRY>

Table 8-1-3

<HEAT>

Table 8-1-4

Model name

RAS-13UAV-E2

Compressor revolution (rps)

To 16.8

To 57.4

From 58.0

Outdoor temp. sensor TO

TO

5

°

C

390

650

840

TO

<

5

°

C

650

650

840

ECONO. operation

TO

5

°

C

390

390

650

TO

<

5

°

C

390

650

650

TO is abnormal

390

650

840

Model name

RAS-13UAV-E2

Compressor revolution (rps)

To 13.8

To 34.7

From 35.3

TO

38

°

C

390

840

840

Outdoor temp. sensor TO

TO

<

38

°

C

390

700

840

TO < 15

°

C

390

TO

38

°

C

390

700

840

ECONO. operation

TO

<

38

°

C

390

390

700

TO

<

15

°

C

390

TO is abnormal

700

700

840