8-3. Temporary Operation

•

Temporary Auto operation, existence of Auto
Restart, and Temporary Cooling operation can be
set by the TEMPORARY button of the indoor
controller.

Fig. 8-3-1

Table 8-3-1

8-3-1. Temporary auto operation

•

When the TEMPORARY button is pushed, the
Auto operation with set temperature fixed at 25

°

C

starts. Controlling is same as that of Auto opera-
tion by the remote controller.

•

When the TEMPORARY button is pushed again,
the operation stops.

•

During Temporary Auto operation, operation by the
remote controller is accepted.

•

Using the Auto Restart function, the Temporary
Auto operation starts when power failure is reset.

8-3-2. Temporary cooling operation

•

When the TEMPORARY operation button keeps
pushed for 10 seconds, Cooling operation of
which compressor motor speed and the indoor fan
speed are fixed starts.

Compressor motor speed :

13 : 30 rps

Indoor fan speed : Low

•

When the TEMPORARY operation button is
pushed again, the operation stops.

•

Auto Restart function is unavailable.

TEMPORARY button

TEMPORARY button

TEMPORARY button

OFF

→

ON

After pushing button

for 3 seconds

After pushing button

for 10 seconds

Control

Temporary Auto operation start

Auto Restart

control select

Temporary Cooling

operation start