8-3. Temporary Operation

Temporary Auto operation, existence of Auto
Restart, and Temporary Cooling operation can be
set by the TEMPORARY button of the indoor
controller.

Fig. 8-3-1

Table 8-3-1

8-3-1. Temporary auto operation

When the TEMPORARY button is pushed, the
Auto operation with set temperature fixed at 25

°

C

starts. Controlling is same as that of Auto opera-
tion by the remote controller.

When the TEMPORARY button is pushed again,
the operation stops.

During Temporary Auto operation, operation by the
remote controller is accepted.

Using the Auto Restart function, the Temporary
Auto operation starts when power failure is reset.

8-3-2. Temporary cooling operation

When the TEMPORARY operation button keeps
pushed for 10 seconds, Cooling operation of
which compressor motor speed and the indoor fan
speed are fixed starts.

Compressor motor speed :

13 : 30 rps

Indoor fan speed : Low

When the TEMPORARY operation button is
pushed again, the operation stops.

Auto Restart function is unavailable.

TEMPORARY button

TEMPORARY button

TEMPORARY button

OFF

ON

After pushing button

for 3 seconds

After pushing button

for 10 seconds

Control

Temporary Auto operation start

Auto Restart

control select

Temporary Cooling

operation start