Toshiba RAS-13UAV-E2 User Manual

Page 57

Advertising
background image

– 56 –

FILE NO. SVM-03008

10-4-2. Caution at servicing

(1) After servicing, push the START/STOP button to return to the normal mode.
(2) After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power

supply again so that memory in the microcomputer returns the initial status. However, the check codes are
not deleted even if the power supply is turned off because they are stored in the fixed memory.

Table 10-4-1

Block distinction

Operation of diagnosis function

Judgment and action

Check

Block

Check

Cause of operation

Air conditioner

Remarks

code

code

status

Short-circuit or disconnec-
tion of the room
temperature sensor
(TA sensor).

Being out of place,
disconnection, short-circuit,
or migration of heat
exchanger sensor
(TC sensor)

Lock of indoor fan or trouble
on the indoor fan circuit

Trouble on other indoor
P.C. boards

Return serial signal is not
sent to indoor side from
operation started.
(1) Defective wiring of

connecting cable

(2) Operation of

compressor thermo.
Gas shortage
Gas leak

Operation command signal
is not sent to outdoor side.

Operation
continues.

Operation
continues.

All off

Operation
continues.

Operation
continues.

Operation
continues.

Displayed when
error is detected.

Displayed when
error is detected.

Displayed when
error is detected.

Displayed when
error is detected.

Flashes when
trouble is
detected on
return serial
signal, and
normal status
when signal is
reset.

Flashes when
trouble is
detected on
operation
command signal,
and normal status
when signal is
reset.

1. Check the room temp. sensor.
2. When the room temp. sensor is

normal, check P.C. board.

1. Check heat exchanger sensor.
2. When heat exchanger sensor is

normal, check P.C. board.

1. Check P.C. board.
2. When P.C. board is normal, check

the motor.

Replace P.C. board.

1. When the outdoor unit never

operate:
(1) Check connecting cable, and

correct if defective wiring.

(2) Check 25A fuse of inverter

P.C. board

(3) Check 3.15A of inverter

P.C. board.

2. To display [Other] block during

operation, check compressor
thermo. operation and supply gas
(check gas leak also).

3. Unit operates normally during

check.
If Return serial signal does not
stop between

2

and

3

of the

indoor terminal block, replace
inverter P.C. board.
If signal stops between indoor
terminal block

2

and

3

, replace

indoor P.C. board.

If return serial signal does not stop
between indoor terminal block

2

and

3

, replace inverter P.C. board.

If signal stops between indoor
terminal block

2

and

3

, replace

indoor P.C. board.

Indoor
P.C.
board
etc.

Not
displayed

Connec-
ting cable
and serial
signal

Advertising
This manual is related to the following products: