Specifications, 1. specifications – Toshiba RAS-13UAV-E2 User Manual

Page 4

Advertising
background image

– 3 –

FILE NO. SVM-03008

1. SPECIFICATIONS

1-1. Specifications

Unit model

Indoor

RAS-13UKV-E2

Outdoor

RAS-13UAV-E2

Current limited

Cooling capacity

(kW)

3.5

Cooling capacity range

(kW)

0.9 – 4.0

Heating capacity

(kW)

4.2

Heating capacity range

(kW)

0.9 – 6.0

Power supply

220 – 240V –1Ph –50/60Hz

Electric

Indoor

Operation mode

Cooling

Heating

characteristics

Running current

(A)

0.15

0.15

Power consumption

(W)

30

30

Power factor

(%)

87

87

Outdoor

Operation mode

Cooling

Heating

Running current

(A)

4.65

5.01

Power consumption

(W)

1020

1100

Power factor

(%)

95

95

Starting current

(A)

5.31

COP (Cooling / Heating)

3.33/3.72

Operation noise

Indoor

High

(Cooling / Heating)

(dB

A)

39/39

Medium

(Cooling / Heating)

(dB

A)

33/34

Low

(Cooling / Heating)

(dB

A)

26/28

Outdoor

(Cooling / Heating)

(dB

A)

48/50

Indoor unit

Unit model

RAS-13UKV-E2

Dimension

Height

(mm)

275

Width

(mm)

790

Depth

(mm)

208

Net weight

(kg)

10

Fan motor output

(W)

30

Air flow rate

(Cooling / Heating)

(m

3

/h)

530/620

Outdoor unit

Unit model

RAS-13UAV-E2

Dimension

Height

(mm)

550

Width

(mm)

780

Depth

(mm)

720

Net weight

(kg)

40

Compressor

Motor output

(W)

750

Type

Twin rotary type with DC-inverter variable speed control

Model

DA91A1F-45F

Fan motor output

(W)

43

Air flow rate

(Cooling / Heating)

(m

3

/h)

2410/2410

Piping connection

Type

Flare connection

Indoor unit

Liquid side

6.35

Gas side

9.52

Outdoor unit

Liquid side

6.35

Gas side

9.52

Maximum length (Per unit)

(m)

15

Maximum chargeless length

(m)

15

Maximum height difference

(m)

10

Refrigerant

Name of refrigerant

R410A

Weight

(kg)

0.9

Wiring connection

Power supply

3 Wires: includes earth (Outdoor)

Interconnection

4 Wires: includes earth

Usable temperature range

Indoor

(Cooling / Heating)

(

°

C)

21 – 32 / 0 – 28

Outdoor

(Cooling / Heating)

(

°

C)

10 – 43 / –10 – 24

Accessory

Indoor unit

Installation plate

1

Wireless remote control

1

Remote controller holder

1

Flat head wood screw

2 (

3.1 x 16L)

Purifying filter

1

Zeolite filter

1

Batteries

2

Mounting screw

6 (

4 x 25L)

Installation manual

1

Owner’s manual

1

Outdoor unit

Drain nipple

1

The specification may be subject to change without nitice for purpose of improvement.

Advertising