Water piping — multiple zones, Gold cgs gas-fired water boiler — boiler manual, Piping multiple zones – Weil-McLain GOLD CGS 550-110-260/0508 User Manual

Page 16

Advertising
background image

Part number 550-110-260/0508

16

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Water piping — multiple zones

3c

Piping multiple zones

Follow instructions on pages 14 and 15 to install near-
boiler or single-zone piping. (Also refer to

Piping for

radiant heating systems or converted gravity sys-
tems

, below, if applicable.)

See

Figure 6

or

Figure 7

, page 17, to complete instal-

lation.

Zoning with circulators (Figure 6)

(return temp over 130°F)

1. Size each circulator to individual circuit require-

ments.

2. Do not install circulator on boiler (except for pri-

mary/secondary piping).

3. Install isolation (balancing) valves to adjust fl ow to

distribute heat to all zones.

4. Install and wire a separate relay for each zone cir-

culator.

Zoning with zone valves (Figure 7)

(return temp over 130°F)

1. Install isolation (balancing) valves to adjust fl ow to

distribute heat to all zones.

2. Provide a separate 24-volt transformer to power the

zone valves. Size the transformer to handle the total
rated load of all connected zone valves.

Piping for radiant heating
systems or converted gravity
systems

Converted gravity (or steam) systems

Whenever possible, use the primary/secondary piping
shown in

Figures 8

or

9

on page 19. This piping design

allows changing boiler fl ow rate without affecting pri-
mary circuit fl ow rate.
If

Figures 8

or

9

cannot be used, use the boiler-bypass

piping shown in

Figure 10

or

Figure 11

on page 21. You

can also use the piping shown in

Figure 12

on page 23

(system-bypass), if the reduced fl ow rate in the heating
system will not cause heat distribution problems.

Failure to prevent low return water
temperature to the boiler could
cause corrosion of the boiler sec-
tions or burners, resulting in severe
personal injury, death or substantial
property damage.

Radiant heating systems

Preferably, use primary/secondary piping, as shown
in

Figures 8

or

9

on page 19. Alternatively, use the

method of either

Figure 10

or

Figure 11

on page 21.

Do not use the piping of Figure 12

(system-bypass),

because this method does not control radiant system
supply temperature.
If radiant system tubing has no oxygen barrier, a

heat

exchanger

must be used.

Radiant heating system piping should include a means of regulating the boiler return water

temperature and the system supply temperature (such as provided by an injection pumping
control). Boiler return water temperature will be adequately controlled using the methods
shown in this manual provided the system supply temperature is relatively constant.

DO NOT

apply the methods in this manual if the system is equipped with an

outdoor reset

control

. Instead, provide controls and piping which can regulate the boiler return water

temperature at no less than 130°F regardless of system supply temperature. Contact your
Weil-McLain representative for suggested piping and control methods. Failure to prevent
cold return water temperature to the boiler could cause corrosion damage to the sections
or burners, resulting in possible severe personal injury, death or substantial property
damage.

Advertising