GOLD CGs Gas-Fired Water Boiler — Boiler Manual

1

Boiler isolation (balancing) valves

2

Flow/check

valve

3

System or zone circulator

4

System temperature gauges

5

Zone

valve

6

Drain

valve

7

System temperature valves (see instruc-

tions to the left for adjusting valves)

8

Blend temperature gauge

9

Relief valve

10

Automatic air vent (with diaphragm-type expansion tank), or

connect to tank fi tting (closed-type expansion tank).

DO NOT

use an automatic air vent when using closed-type expansion
tank. It would allow air to leave the system, causing waterlog-
ging of the expansion tank.

11

Fill valve

12

Diaphragm-type or bladder-type expansion tank, if used (For

closed-type expansion tank, pipe from top of air separator to
tank fi tting as in

Figure 5

, page 15.)

13

Air separator and automatic vent, if used (Note that the

fi ll valve must always be connected to the expansion tank,
regardless of location of expansion tank, circulator or air
separator.)

Figure 8

Primary/secondary piping
Zoning with circulators

Figure 9

Primary/secondary piping
Zoning with zone valves

3d

Piping — low temp systems