Burners, base and inlet air box

The boiler contains ceramic fi ber and fi berglass

materials. Use care when handling these materials
per instructions on page 68 of this manual. Failure
to comply could result in severe personal injury.

If insulation is damaged or displaced, do not operate

the boiler. Replace or reposition insulation as neces-
sary. Failure to replace damaged insulation can result
in a fi re hazard, causing severe personal injury, death
or substantial property damage.

1. After turning off power to the boiler, remove the inlet air box top panel

(

Figure 27

, item

13

, page 56).

2. Inspect gasket (item

14

). Replace if necessary.

3. Inspect burners and all other components in the inlet air box and boiler

base.

4. If burners must be cleaned, fi rst remove item

11

,

Figure 27

, page 56.

Access the burner assembly by fi rst removing burner baffl e, item

4

. Then

remove the screws securing the burner tray to the manifold. Slide the
burner tray out. Follow

Burner cleaning instructions

below to clean

burners thoroughly.

6. Inspect the base insulation. Pay attention to the

WARNING

on page 64

regarding working with insulation materials. Verify that the insulation
is intact and secure against all four sides of the base.

7. Replace all components when service has been completed.

Burner cleaning instructions

Airborne materials, such as fi berglass and dust, are pres-
ent during construction and remodeling. These materi-
als can be drawn in with the combustion air and obstruct
burner ports, resulting in carbon monoxide production,
a fi re hazard, or building freeze damage. Read and follow
the

WARNING

on page 9. Failure to inspect and clear

gas burner ports could result in severe personal injury,
death or substantial property damage.

1. Inspect each burner to insure that every port is completely open.

2. If any port is not completely clear, run a vacuum at the burner inlet

while cleaning the burner ports with a wire brush. The vacuum will
help to draw any airborne material out of the burner.

3. Follow instructions above to replace all components after cleaning.

Condensate drain system

1. Inspect condensate drain fi ttings and tubing. Verify

that condensate can fl ow freely to drain.

Service . . .

Inducer motor

1. With boiler power

off

, place a few drops of S.A.E.

20 motor oil in each of the two oil cups.

Use

only

S.A.E. 20 motor oil

to

lubricate the inducer motor. Do not
use universal household oils. Motor
could be damaged, resulting in pos-
sible severe property damage.

Oiled-bearing circulators

1. The circulator shipped with the CGs boiler is water-

lubricated. No oiling is required.

2. Check other circulators in the system. Oil any

circulators requiring oil, following circulator man-
ufacturer’s instructions. Over-oiling will damage the
circulator.

Start-up . . .

1. Perform all start-up procedures in Section

7

of this

manual.

2. Verify

cold fi ll pressure

is correct and that fi ll system

is working properly.

3. Verify

antifreeze level

(if used) is at the right con-

centration and that inhibitor level is correct.

4.

Check gas piping

, per manual Sections

5

and

7

,

verifying no indications of leakage and all piping
and connections are in good condition.

5. Read

the

Operating instructions

(Section

9c

of this

manual or on boiler label) applying to the boiler.

6. Start the boiler following the

Operating instruc-

tions

(Section

9c

of this manual or on boiler label)

and manual Section

7

.

Advertising