Service & maint. — annual start-up

continued

10b

Check/test . . .

Gas piping

1. Sniff near fl oor and around boiler area for any in-

dication of a

gas leak

.

2.

Test gas piping using bubble test,

per Section

5

of this manual, if there is any indication of a leak.

Cold fi ll and operating pressures

1. While the system is cold, note the

pressure reading

on the boiler pressure/temperature gauge. Verify that
cold fi ll pressure is correct.

2.

Watch the pressure

as the boiler and system heat

up to ensure pressure rise is normal. Too high a rise
would indicate a waterlogged or undersized expan-
sion tank.

Air vents and air elimination

1. Inspect automatic air vents (if used). Also inspect

air separators to ensure they are operational.

2. The cap must be unscrewed one turn to allow air to

escape.

3. See

Figure 22

. If the air vent is leaking, remove cap

A

and briefl y push valve

B

and then release to clean

the valve seat.

4. Replace

cap

A

by twisting all the way onto valve

B

and then unscrewing one turn.

Figure 22

Automatic air vent, typical

Limit controls and cutoffs

1. Inspect and test the boiler limit control. Verify op-

eration by turning control set point below boiler
temperature. Boiler should cycle off. Return dial to
original setting.

2. Inspect and test additional limit controls or low

water cutoffs installed on system.

Expansion tank

1. Expansion tanks provide space for water to move in

an out as the heating system water expands due to
temperature increase or contracts as the water cools.
Tanks may be open, closed or diaphragm or bladder
type. See Section

3

of this manual for suggested best

location of expansion tanks and air eliminators.

Open-type

— located above highest radiator or

baseboard unit, usually in the attic or closet. Has a
gauge glass and overfl ow pipe to a drain.

Closed-type

— welded gas tight and located above

boiler. Tank is partially fi lled with water, leaving an
air cushion for expansion.

Make sure this type of tank is fi tted with a

tank

fi tting

, such as the B & G Tank-Trol or Taco

Taco-Trol. This fi tting reduces gravity circula-
tion of air-saturated tank water back to the
system and prevents the air from bubbling up
through the water as it returns from the sys-
tem.

Do not use automatic air vents in systems
with closed-type tanks.

The air will escape

from the system instead of returning to the tank.
Eventually, the tank will waterlog and no longer
control pressurization. The boiler relief valve
will weep frequently.

Diaphragm- or bladder-type

— welded gas tight

with a rubber membrane to separate the tank pres-
surizing air and the water. May be located at any
point in the system, but most often found near the
boiler.

Systems with this type of expansion tank require
at least one

automatic air vent

, preferably lo-

cated on top of an air eliminator, as shown in
examples in manual Section

3

.

2. If relief valve has tended to weep frequently, the ex-

pansion tank may be waterlogged or undersized.

Closed-type tank

— tank is most likely water-

logged. Install a tank fi tting if not already installed.
Then check fill level per fitting manufacturer’s
instructions. If fi ll level is correct, check tank size
against manufacturer’s instructions. Replace with
a larger tank if necessary.

Diaphragm- or bladder-type

— fi rst, check tank

size to be sure it is large enough for the system. If
size is too small, add additional tank(s) as neces-
sary to provide suffi cient expansion. If tank size is
large enough, remove tank from system and check
charge pressure (usually 12 psig for residential ap-
plications). If tank won’t hold pressure, membrane
has been damaged. Replace tank.