Troubleshooting — air pressure switch

11b

Air pressure switch

Make sure boiler water temperature
is 100 °F or cooler before starting
procedure to obtain appropriate
readings.

Check pressure switch setting

1. See

Figure 24

and

Table 6

.

2. Remove both air pressure switch hoses from air

pressure switch.

3. Install tees and tubing as shown in

Figure 24

to

inclined manometer.

4. Turn off gas valve and set thermostat to call for heat.

Inducer will run but burners will not ignite.

5. Check for 24 VAC between both air pressure switch

terminals and ground.

6. If manometer reading is above the setpoint of the

switch (see

Table 6

), but there is not 24 VAC between

both air pressure switch terminals and ground
— replace air pressure switch.

Figure 24

Manometer connections

Table 6

Pressure switch setpoint

(for elevations above 2,000 ft, contact your
local Weil-McLain sales offi ce for details.)

Boiler model number

Inches W.C.

CGs-3

1.79"

CGs-4

1.48"

CGs-5

1.22"

CGs-6

0.95"

Troubleshooting air pressure reading

1. If manometer reading is lower than the setpoint

of the switch (see

Table 6

) — check for possible

causes:

blockage in hoses

obstruction in inducer housing outlet

loose inducer wheel on motor shaft

inducer motor not in proper rpm

inducer back plate not sealed properly

blockage in block assembly

blockage in fl ue pipe or termination

incorrect pressure switch

Return to normal operation

When pressure reading is correct and air pressure switch
is operating properly — remove tees and reinstall hoses
to air pressure switch.

The boiler will not operate cor-

rectly unless pressure switch
hoses are correctly located.
The red hose connects from
the right side (negative) hose
barb to the fl ue collector. The
white hose connects from the
left side (positive) hose barb
of the switch to the connector
box (between flue collector
and inducer) as shown in

Figure 24

.