Please read before proceeding, Gold cgs gas-fired water boiler — boiler manual, Installer – Weil-McLain GOLD CGS 550-110-260/0508 User Manual

Page 5: User

Advertising
background image

Part number 550-110-260/0508

5

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Please read before proceeding

Installer

Read all instructions before in-
stalling.

Follow all instructions in

proper order to prevent personal
injury or death.

Also refer to CGs

Venting Supplements

.

• Consider

piping and installation

when determining

boiler location.

• Any

claims for damage or shortage in shipment

must be fi led immediately against the transportation
company by the consignee.

User

This manual is for use only by your qualifi ed
heating installer/service technician.

Please refer to the

User’s Information Manual

for

your reference.

• We recommend regular

service by a qualifi ed

service technician, at least annually

.

When calling or writing about the boiler— Please have the boiler model number from the
boiler rating label and the CP number from the boiler jacket. You may list the CP number in
the space provided on the Installation and service certifi cate found on page 30.

The boiler contains ceramic fi ber and fi berglass materials. Use care when handling these
materials per instructions on page 64 of this manual. Failure to comply could result in severe
personal injury.

Failure to adhere to the guidelines on this page can result in severe personal injury, death
or substantial property damage.

• Continual fresh makeup water will reduce

boiler life. Mineral buildup in sections reduces
heat transfer, overheats cast iron, and causes
section failure. Addition of oxygen and other
gases can cause internal corrosion. Leaks in
boiler or piping must be repaired at once to
prevent makeup water.

Do not add cold water to hot boiler. Thermal
shock can cause sections to crack.

Glycol — potential fi re hazard —

All glycol is fl ammable when exposed to high
temperatures. If glycol is allowed to accumulate
in or around the boiler or any other potential
ignition source, a fi re can develop. In order to
prevent potential severe personal injury, death
or substantial property damage from fi re and/or
structural damage:

Never store glycol of any kind near the boiler
or any potential ignition source.

• Monitor and inspect the system and boiler

regularly for leakage. Repair any leaks im-
mediately to prevent possible accumulation
of glycol.

• Never use automotive antifreeze or ethylene

glycol in the system. Using these glycols can
lead to hazardous leakage of glycol in the
boiler system.

When servicing boiler —

• To avoid electric shock, disconnect electrical supply

before performing maintenance.

• To avoid severe burns, allow boiler to cool before

performing maintenance.

Boiler operation —

• Do not block fl ow of combustion or ventilation air

to boiler.

• Should overheating occur or gas supply fail to shut

off, do not turn off or disconnect electrical supply to
circulator. Instead, shut off the gas supply at a location
external to the appliance.

• Do not use this boiler if any part has been under

water. Immediately call a qualifi ed service techni-
cian to inspect the boiler and to replace any part of
the control system and any gas control that has been
under water.

Boiler water —

• Do not use petroleum-based cleaning or sealing

compounds in boiler system. Water seal deterioration
will occur, causing leakage between sections. This can
result in substantial property damage.

Do not use “homemade cures” or “boiler patent medi-
cines”. Serious damage to boiler, personnel and/or
property may result.