Troubleshooting — control module lights, Gold cgs gas-fired water boiler — boiler manual – Weil-McLain GOLD CGS 550-110-260/0508 User Manual

Page 53

Advertising
background image

Part number 550-110-260/0508

53

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Troubleshooting — control module lights

(cont.)

11d

CHART 7 — Insufficient heat or no heat to system (POWER light on steady)

Electrical shock hazard — Wherever you see TURN OFF POWER , follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.

• Replace rollout switch.

• Boiler is in standby.
• Set thermostat to call for

heat and recheck
operation.

• Verify Sequence of

operation, Figure 18,
page 31.

Replace control module.
Retest.

• Boiler water temperature exceeded

setting on limit switch with thermostat
calling for heat. Boiler is OK. (See normal
sequence of operation, Figure 18, p. 31.)

• Also check setting on limit switch (should

be above 140°F.).

• Has it been at least 5 minutes since setting thermostat to

call for heat? If not, wait 5 minutes. Is system heating?

• Is thermostat set to call for heat? Remove thermostat

wires at boiler and check continuity across the two wires.
If circuit isn't closed, check external thermostat (zone
valve, relay, etc.) wiring. Correct problems and retry.

• Reconnect external thermostat wiring at boiler.

Is thermostat circuit closed (continuity across wires)?

• If you have sufficient heat — boiler should be in normal

operating sequence. (See normal sequence of operation,
Figure 18, page 31.)

• If you have less than sufficient heat —

Is vent or combustion air piping free of blockage?

No

Yes

• Correct conditions and

recheck operation.

• See Figure 18, page 31

for normal sequence of
operation.

Contact your Weil-McLain
sales representative.

• Replace control

module.

• Retest.

• Repair/replace

circulator. Retest.

• Repair/replace

wiring. Retest.

• Remove CIRCULATOR harness plug from

CIRCULATOR plug receptacle (Figure 25, Item
7
, page 46
). Check with voltmeter across pins of
control module receptacle.

Does voltmeter show 120 VAC across pins?

No

Yes

Is boiler System circulator operating?

• Wait 5 minutes.

Is FLAME light on?

No

Yes

• Wait for boiler water to cool to temperature 20 to 30 °F

lower than temperature set on limit switch.

Are limit switch contacts closed?

Is LIMIT light on?

No

Yes

Are all red lights off?

No

Yes

Wait 30 seconds.
Are all red lights off?

No

Yes

• Replace control module.
• Retest.

• Check limit switch

contacts with continuity
checker.

Are limit switch contacts

closed?

No

Yes

No

Yes

No

Yes

• Replace

limit switch.

• Retest.

No

Yes

Check rollout switch

continuity — is switch

closed?

No

Yes

• Check any other

limit controls wired
into the limit
circuit. If all are
OK, then replace
control module.

• Retest.

If rollout thermal fuse element has
opened, determine cause and
correct condition. Failure to do so
will cause severe personal injury,
death or substantial property
damage.