GOLD CGs Gas-Fired Water Boiler — Boiler Manual

1

Boiler isolation (balancing) valves

2

Flow/check

valve

3

System or zone circulator

4

System temperature gauges

5

Zone

valve

6

Drain

valve

7

System temperature valves (see instructions to the left

for adjusting valves)

8

Blend temperature gauge

9

Relief

valve

10

Automatic air vent (with diaphragm-type expan-

sion tank), or connect to tank fi tting (closed-type
expansion tank).

DO NOT

use an automatic air

vent when using closed-type expansion tank. It
would allow air to leave the system, causing wa-
terlogging of the expansion tank.

11

Fill valve

12

Diaphragm-type or bladder-type expansion tank,

if used (For closed-type expansion tank, pipe from
top of air separator to tank fi tting as in

Figure 5

,

page 15.)

13

Air separator and automatic vent, if used (Note

that the fi ll valve must always be connected to the
expansion tank, regardless of location of expansion
tank, circulator or air separator.)

Figure 10

Boiler-bypass piping
Zoning with circulators
Alternative to primary/secondary piping
Figures 8

and

9)

Figure 11

Boiler-bypass piping
Zoning with zone valves
(Alternative to primary/secondary piping
Figures 8

and 9

)

3d

Piping — low temp systems

(continued)