Introduction

1–4

152606

System Specifications

The PV225S has been designed for photovoltaic power systems, which operate
within the following specifications.

Electrical Specifications

Table 1-1 provides the AC and DC specifications for the PV225S.

Over Voltage, Under Voltage and Frequency Ranges

Table 1-2 provides the over voltage, under voltage, over-frequency, and
under-frequency detection limits for the PV225S. These detection limits have
been factory tested and deemed to be in compliance with IEEE-292 and UL 1741
requirements for utility interaction.

CAUTION: Equipment Damage

Operation of the PV225S in a manner other than specified in this manual may cause
damage to the PV225S and other system components and will void the terms of the
warranty.

Table 1-1 Electrical Specifications

Specification

PV225S-480-P

Nominal AC Input Voltage
(+10% to -12% acceptable range)

480 Vac
(422 to 528 Vac)

Maximum AC Output Current

271 A

rms

Nominal AC Input Frequency
(+0.5 to -0.7 Hz acceptable range)

60 Hz
(59.3 to 60.5 Hz)

Output Power

225 kW

Peak Power Tracking Window

300 to 600 Vdc

Maximum Open Circuit Voltage

600 Vdc

Maximum DC Input Current

781 amps

Table 1-2 Over/Under Voltage and Over/Under Frequency Ranges


Vac Condition
(% of Nominal)

PV225S-480-P

Voltage Range

Trip Time

Vac < 50%

Vac < 240

6 cycles

50% <

Vac < 88%

240 < Vac <

422

2 seconds

88% <

Vac < 110%

422 < Vac <

528

normal operation

110% < Vac < 137%

528 < Vac < 657

2 seconds

137% < Vac

657 < Vac

2 cycles

f < rated -0.7

f < 59.3

6 cycles

f > rated +0.5

f > 60.5

6 cycles