On/Off Switch

The PV225S

incorporates a maintained position O

N

/O

FF

switch (S3) located on

the front door of the main enclosure. Under normal conditions, the O

N

/O

FF

switch

is in the O

N

position. Turning the switch to the

OFF

position will initiate an

immediate controlled shutdown of the PV225S

and opens both the main AC and

DC contactors within the unit. The main AC and DC contactors cannot be closed
unless the switch is in the

ON

position. The PV225S

is prevented from being

restarted until the O

N

/O

FF

switch is turned back to the O

N

position.

WARNING: Shock Hazard

Disengaging the main enclosure door interlock switch does NOT remove all hazardous
voltages from inside the inverter. Before attempting to service the PV225S, follow the
de-energize Lockout and Tag procedure on page x.

WARNING: Shock Hazard

Turning the O

N

/O

FF

switch to the O

FF

position does NOT remove all hazardous voltages

from inside the inverter. Before attempting to service the PV225S, follow the de-energize
Lockout and Tag procedure on page x.