Mounting and Anchoring the Units

152606

3–5

Mounting and Anchoring the Units

To mount and anchor the PV225S:

1.

Predrill the floor or pad to accept 1/2" diameter masonry anchors or ensure it
has pre-installed anchoring bolts that will fit the 5/8" mounting holes.

2.

Lift the main inverter from beneath the lower enclosure with a forklift or
pallet jack as shown in Figure 3-2 on page 3–4. Move the Main Inverter
Enclosure into place.

3.

Lift the AC Interface/Transformer assembly from beneath the enclosure with
a forklift or pallet jack as shown in Figure 3-2 on page 3–4. Move the AC
interface/transformer assembly into place.

4.

Secure the Main Inverter Enclosure feet to the floor with a 1/2" diameter
anchor bolts.

5.

Secure the AC Interface/Transformer assembly enclosure feet to the floor
with 1/2" diameter anchor bolts.

Important:

Before proceeding with the installation, determine the location and layout

of the components, conduit penetration locations, conductor and conduit sizing, and
method for anchoring the unit. Ensure adequate space is provided for clearance for
ventilation and serviceability. Review Chapter 2, “Planning” if necessary before
proceeding.

Figure 3-3 Mounting Hole Locations

Mounting Holes for
securing and anchoring
the units.