PC Communications

152606

3–23

Direct Connection

The direct connection provides the means to use the features of the GUI by
connecting a PC directly to the CCU. This allows field personnel to monitor and
control the inverter from a nearby laptop computer directly connected by a serial
cable. The computer connects to the inverter directly through one of its serial
COM ports running at 9600 baud.

The installed RS232/FO Converter will have to be removed and minor re-wiring
will be required.

The RS232/FO Converter kit (Xantrex p/n 1-152624-01) is required for this
connection to change the communication protocol from ethernet to serial in the
Communications Enclosure. A DB25-to-DB25 gender-changer adapter and
DB9/DB25 serial cable are provided with the RS232/FO Converter kit to
complete the connection.

If connecting the PC directly to the inverter:

1.

Open the Communications Enclosure.

2.

Disconnect the TX (transmit-orange) and RX (Receive-blue) wires from the
installed RS232/FO Converter in the Communications Enclosure.

3.

Disconnect the power plug from the installed converter and plug it into the
new RS232/FO Converter.

4.

Remove the installed converter. Replace with the new RS232/FO Converter.

5.

Reconnect the TX (transmit-orange) and RX (Receive-blue) wires to the new
Converter in the Communications Enclosure.

6.

Plug the DB25-to-DB25 Gender-changer Adapter into the Serial
Communications Port on the RS232/FO Converter. (Step not shown.)

7.

Plug the DB25 connector on the serial cable into the gender-adapter and the
DB9 connector of the serial cable into the serial port on the computer. (Step
not shown.)

Figure 3-21 RS232/FO Converter Kit Installation

SA2 Surge Arrestor

MultiTech 56K Modem

Modem Power Cord
(Do not Remove)