Pv array connections – Xantrex Technology PV225S-480-P User Manual

Page 67

Advertising
background image

Wiring - Specific

152606

3–19

PV Array Connections

To make the connections from the PV Array/combiner to DC Interface
enclosure:

1.

Remove the door clamps and open the door to the DC Interface Enclosure.

2.

Route the PV Array cables conductors POSitive (PV+), NEGative (PV-), and
PV GND through the conduit to the DC Interface Enclosure, entering on the
underside.

3.

The DC power conductor terminations are made at the S2-6 (POS/DC+), and
K2-6T3 (NEG/DC-) and TB4 (PV Gnd) locations. See Figure 3-19.

4.

Terminations for the S2-6, K2-6T3, and TB4 terminals are made with box
connector using a 1/2" Hex Allen screw. The hardware should be tightened to
a torque value of 600 in-lbs (67.8 Nm).

5.

Close the door to the DC Interface Enclosure and replace the door clamps.

Figure 3-19 PV Array Cable Routing and Terminations

PV NEGative (K2-6T3)

PV POSitive (S2-6)

PV GrouND (TB4)