Visual Inspection of Mechanical Connections

152606

4–3

Visual Inspection of Mechanical Connections

To perform a visual inspection of the PV225S mechanical connections:

Visual Inspection of Electrical Connections

To perform a visual inspection of the PV225S electrical connections:

1.

Ensure that the AC and DC Disconnect Switches, as well as any utility
interconnect circuit breakers or main disconnect switches, are opened.

2.

Ensure all anchor bolts and any required seismic bracing is properly
tightened and in place.

3.

Remove the wiring access panels and front covers from the AC
Interface/Transformer assembly and Main Inverter Inductor Enclosure.

4.

Remove the latches and open the doors of the Main Inverter Enclosure,
the AC and DC Interface Enclosures, and Communication Enclosure
and inspect.

5.

Verify all wire conduit fittings and connections are properly tightened.

1.

Ensure that the AC and DC disconnect switches, as well as any utility
interconnect circuit breakers or main disconnect switches, are opened.

2.

Ensure all conductors and wiring connections interfacing with the
PV225S are tightened to the correct torque value.
For specific torque values, see Table 3-1, “AC Terminal Wire Gauge,
Bolt Size, and Torque Values” on page 3–12 and Table 3-2, “DC
Terminal Wire Gauge, Bolt Size, and Torque Values” on page 3–12.

3.

Verify AC power conductors terminated at TB5, TB6, TB7 within the
Main Inverter Enclosure are terminated correctly and properly
sequenced.

4.

Verify the AC power conductors terminated at S1-2T1, S1-4T2,
and S1-6T3 within the AC Interface Enclosure are terminated correctly
and properly sequenced.

5.

Verify DC power conductors terminated at S2-6, K2-6T3, and TB4
within the DC Interface Enclosure are terminated correctly and properly
polarized.