Xantrex Technology PV225S-480-P User Manual

Page 64

Advertising
background image

Installation

3–16

152606

5.

Connect the AC power conductors in the Main Inverter Enclosure at TB5
(A phase), TB6 (B phase), and TB7 (C phase) with a box connector using a
3/8" Hex screw. This hardware should be tightened to a torque value of
375 in-lb (42.4 Nm). Connect the ground conductor to the TB1 terminal on
the ground bar on the right side of the enclosure. Torque this connection to
420 in-lb (47.5 Nm).

Figure 3-15 AC Terminal Connections in the Main Inverter Enclosure

Figure 3-16 AC Terminal Connections in the AC Interface Enclosure

TB6

TB5

TB7

TB1

Enlargement of
Terminal Connectors
in the AC Interface
Enclosure

AC Interface Enclosure

S1-4T2

(B phase)

S1-2T1

(A phase)

S1-6T3

(C phase)