Section 2. Installation

Load Connection

Release A

31

Figure 2.2 Maximum Load Wire Length for 1 V Line Drop

Noise and Impedance Effects

To minimize noise pickup or radiation, use

shielded pair wiring of shortest possible length for load wires. Connect the shield to
the power supply chassis. Where shielding is impossible or impractical, simply
twisting the wires together will offer some noise immunity.

Making Load

Connections

WIRE GAUGE (AWG)

16

14

12

10

8

6

4

2

1/0

1

2/0

WIRE LENGTH (FEET)

100

90

80

70

60

50

40

30

20

10

LOAD CURRENT (AMPS)

1

2

3

4

5

6 7

8

9 10

20

30

40

50

60

70 80 90 100

200

300

400

500

1000

WARNING
There is a shock hazard at the load when using a power supply with a rated
output greater than 40 V. To protect personnel against accidental contact with
hazardous voltages, ensure that the load, including connections, has no live
parts which are accessible. Also ensure that the insulation rating of the load
wiring and circuitry is greater than or equal to the maximum output voltage of the
power supply.

!

CAUTION
When making connections to the bus bars, ensure that each terminals’ mounting
hardware and wiring assembly are placed to avoid touching the other terminal
and shorting the power supply output. Heavy connecting cables must have some
form of strain relief to avoid loosening the connections or bending the bus bars.