Xantrex Technology XPD 60-9 User Manual

Page 49

Advertising
background image

Section 3. Local Operation

User Diagnostics

Release A

47

Output voltage
fluctuating or
regulation poor.

Is unit at current limit?

Increase current limit setting or
reduce load. See

“Standard

Operation” on page 35

.

Is input voltage within
specified range?

Connect to appropriate AC voltage
source. See

“AC Input Power

Connection” on page 28

.

Are sense lines
connected?

See

“Load Connection” on page

30

, and

“Remote Sensing” on

page 33

.

is unit under remote
analog control?

Ensure that program source is
stable.

Internal circuit.

See your service technician.

Output oscillating.

Internal circuit.

See your service technician.

Symptom

Check

Further Checks and Corrections

Advertising
This manual is related to the following products: