Connections and indicating elements, Mounting, Connections and indicating elements mounting – VEGA TH LINK Version 1.1 Installation Guide User Manual

Page 12

Advertising
background image

Design of the TH LINK

Trebing & Himstedt Prozeßautomation GmbH & Co. KG | TH LINK

12

Connections and indicating elements

[1] Ethernet interface: RJ-45 (10Base-T/100Base-TX)

– LED lights yellow: Ethernet data communication
– LED lights green: physical connection available

[2] LED ETH

– ETH lights red: first start phase
– ETH flashes red: boot procedure
– ETH lights red or flashes red or green in case of an error:

internal firmware failure

– ETH lights green: connection to application via Ethernet

[3] LED RUN

– RUN lights red: internal failure identified
– RUN lights green: 24V power supply is fed

[4] LED BUS

– BUS lights green: device communicates active via

PROFIBUS

[5] PROFIBUS interface: D-Sub socket

[6] Terminal strip for +24 VDC power supply

– A: 24 V (+)
– B: 0 V (-)
– C: not assigned
– D: Earth conductor

Mounting

[8] 35 mm DIN top-hat rail (not included in the scope of
delivery)

Advertising