Bus terminating resistors

Terminations of a PROFIBUS segment must each be terminated
with a bus terminating resistor. Use standardised plugs
containing terminating resistors.

Fig. 8: Bus termination configuration (see standard IEC 61158)

Setting PROFIBUS parameters

Depending on the used application software (not included in the
scope of delivery), the TH LINK can be a passive station (without
an own station address) or an active station (class 2 PROFIBUS
master).

The setting of the PROFIBUS parameters is only required, if you
use the TH LINK as a class 2 master in the operation mode
active/passive PROFIBUS station. The PROFIBUS parameters
are given by the class 1 master.

[1] 390

Ω

Pull-up resistance from pin 3 to positive supply voltage at pin 6

[2] 220

Ω

Cable terminating resistor between pin 3 and pin 8

[3] 390

Ω

Pull-down resistance from pin 8 to data reference potential at

pin 5

Data+

(Pin 3)

Data–

(Pin 8)

GND

DC/DC

(Pin 5)

[2]

[3]

[1]

+5 V

DC/DC

(Pin 6)