Technical data

Trebing & Himstedt Prozeßautomation GmbH & Co. KG | TH LINK

34

Technical data

Electrical data

Nominal supply voltage

(limit values)

VDC

24 (19.2...28.8)

Current consumption max.

mA

190

Protection class

IP

20


Operating conditions

Ambient temperature range °F

32...122

Relative humidity

%

20...80 (no condensation)


Case data

Dimensions W × H × D

in

0.9 x 3.9 x 4.5

Weight (approx.)

l

0.3


PROFIBUS interface

Interface

Type

RS 485

Transmission rate

bps

9,600...12M

Sub-D plug pin assignment

Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Pin 9

not assigned
not assigned
B line data+ (RxD/TxD-P)
RTS
GND (0 V)
Potential (+5 VDC)
not assigned
A line data– (RxD/TxD-N)
not assigned

Other

Ethernet connection

Type

RJ-45 (10Base-T/100Base-TX)

Certificates

CE, UL