Check list, Series two heater – Grain Systems PNEG-584 User Manual

Page 2

Advertising
background image

2

SERIES TWO HEATER

_____

1. Check all wire connections

_____

2. Spark plug and flame sensor tightness set plug gap to 1/8"

_____

3. Check plug in terminal strips on back of circuit board to be sure they are plugged into proper

position.

_____

4. Software settings correct for type of heater (hi-low, on-off)

_____

5. Dip switch settings correct for heater model (slave, master)

_____

6. Most current software version installed

_____

7. Turn heater toggle switch on. Most current software version should be displayed first, fol

lowed by temperature. Screen should read "NO AIRFLOW".

_____

8. Turn fan on. Screen should read "AIRFLOW".

_____

9. Program hi-limit set point to 140 degrees F.

_____

10. Program cycle set point to 120 degrees F (only on hi-lo units).

_____

11. Program differential to 10 degrees F/

_____

12. Turn gas on to heater unit.

_____

13. Press start switch on heater. Screen should flash "PURGE".

_____

14. After 10 second purge heater should light screen, and should read "HI-FLAME".

"FLAME" should appear on lower right hand corner of screen.

_____

15. Adjust pressure to 10 psi (lp units) 5 psi (ng units).

_____

16. Check pipe train for leaks with soapy water.

_____

17. Temperature should rise to 120 degrees. Screen should read "LO-FLAME" and unit

should cycle to lo-flame. (hi-lo units only)

_____

18. Adjust pressure with ball valve to 2 psi (lp units) 1 psi (ng units). (hi-lo units only)

_____

19. On standard units temperature will rise to 140 degrees. Screen will read "OFF-CYCLE".

Heater will shut off at this point.

_____

20. Temperature will drop 10 degrees and unit will cycle back to hi-flame. Screen should read

"HI-FLAME".

_____

21. Observe unit go through 3 cycles.

_____

22. Pull wire off of housing hi-limit switch. Screen should read "ERROR 000" and "HOUSING

TEMP HI-LIMIT". Heater should shut down and lock out. Fan should shut off.

_____

23. Turn heater toggle switch on. Most current software version should be displayed first,

followed by temperature. Screen should read "NO AIRFLOW".

_____

24. Turn fan on. Screen should read "AIRFLOW".

_____

25. Press start switch on heater. Screen should flash "PURGE".

_____

26. After 10 second purge heater should light. Screen should read "HI-FLAME". "FLAME" should

appear on lower right hand corner of screen.

_____

27. Shut gas off to heater and allow gas to burn out of system.

_____

28. 2-4 seconds after flame goes out on heater, "FLAME" in lower right hand corner of screen

should go out. Unit should begin to spark.

_____

29. After 10 seconds fan and heater should shut down and lock out. Screen should read

"ERROR 000" and "FLAME OUT".

_____

30. Check heater visually to see that all decals are in place and correctly located.

_____

31. Place owners manual in control box.

Tester Signature___________________________________________

Date____________________________________

CHECK LIST