Advanced settings / options – Xylem IM229 R06 Aquavar SOLO User Manual

Page 11

Advertising
background image

11

6: ADVANCED SETTINGS / OPTIONS

WHEN TO USE ADVANCED SETTINGS
• Failure of the controller to go into standby mode (pump

stopped) is sometimes caused by the tank or check valve.

First insure that the tank pre-charge pressure is correct,

refer to Tank Sizing and Setting section. The system

must be drained to properly check the tank pre-charge

pressure. A faulty check valve or system leak will allow

a system pressure drop preventing the controller from

shutting down as it will see flow. Spring type check valves

should be used for every 200’ of vertical pipe and one on

the pump side of the tank and pressure sensor. If the tank

and check valve appear to be operating correctly, use the

instructions and chart in Size of Pressure Variation for

Flow Detection in this section to make a program change.

• If the controller stops momentarily when there is plenty

of flow - see instructions to increase pressure variation in

Size of Pressure Variation for Flow Detection.

• If a Dry Well fault (2 red blinks) is not detected when

the well is dry, first ensure the motor overload setting is

correct. Then perform the Dry Well Power Calibration

while the system is at maximum flow (open several

faucets) and the pressure setting is normal. It may be

necessary to change the Dry Well Trigger Conditions to

Power Only or Pressure Only.

• If the Dry Well fault (2 red blinks) occurs when there is

plenty of water available, perform the Dry Well Power

Calibration while there is low flow and the pressure

setting is high.

• If a Dry Well is impossible e.g. pumping from a lake, it

can be disabled.

Most applications do not require changes to these advanced

settings. They are provided for the occasional application

that requires more flexibility to achieve desired results.
Advanced Settings include:
• Trigger conditions for No Water/Loss of Prime Fault
• Calibration of power threshold used for No Water/Loss of

Prime Fault

• Dry Well Restart Time Fixed or Progressive
• Size of pressure variation used for No Flow detection
Note: In the text below, “Dry Well” and “No Water/Loss of

Prime” mean the same thing.

HOW SETTINGS ARE CHANGED
Advanced settings are made by holding down pushbutton(s)

while at the same time switching a DIP switch in a specific

direction. In all cases, power to the controller must be on

and the pump stopped in order to make the desired change.

If needed, the pump can be forced to stop by disconnecting

one wire from the switch input terminal block.
After settings have been changed, the controller must run

and stop the pump for the setting to be stored in memory.

Once this is done, removing power will not affect settings.

There is no limit to how many times the settings can be

changed.

Settings are described below. Where applicable, after a

description, there is a table showing which pushbutton(s)

and DIP switch to use to make a particular setting. The

tables show which pushbutton(s) to hold down, which DIP

switch to flip and the direction to flip it. If the DIP switch is

in the wrong starting position, move it before pressing the

pushbutton.
For example, suppose a setting calls for flipping a DIP

switch from left to right but it is already in the right

position. In that case, before pressing any pushbuttons, you

would first flip the switch to the left position. Then you

would press the pushbutton and flip the switch to the right.
You can switch the DIP switches all you want without

affecting any of the advanced settings as long as no

pushbuttons are pressed. You can change settings as many

times as you want. Be sure to put DIP switches back in the

required positions after the setting are done.

RESETTING THE FACTORY DEFAULTS
Controller settings can always be returned to factory

defaults by pressing both pushbuttons for 10 or more

seconds while controller is powered and the pump is

stopped. Default controller settings are:
• Pressure Setting = 50 PSI
• Dry Well trigger = Low Pressure AND Low Power
• Dry Well power level = factory default which is based on

motor overload switch

• Dry Well restart time = increasing 1/10/20/30/60 min.
• Pressure variation = +/-2 PSI.

DRY WELL TRIGGER CONDITIONS
Dry Well fault has four choices for trigger conditions. The

factory default is to trigger when power and pressure are

both low. This is the best choice for most applications. The

other three choices are Low Power only, Low Pressure only

and disabled. Low Pressure is defined as being less than 75%

of pressure setting.

Pushbutton

DIP Switch

Direction to

Dry Well Trigger Condition

to Hold

to Flip

Flip

Down

DIP Switch

Low Pressure + Low Power*

Top

Left to Right

Low Pressure Only

Top

Right to Left

Low Power Only

Bottom

Left to Right

Disabled

Right to Left

* Factory Default

DRY WELL POWER CALIBRATION
While pump is pumping water press and hold both

pushbuttons until LED turns orange. This will calibrate

the power level at which the Dry Well fault occurs. This

calibration is especially important when Low Power only

is used as the trigger condition. Hold the pushbuttons

for at least 3 seconds to get the LED to turn orange. The

controller requires the pump to be running at least at 75%

of full speed before allowing calibration. If the LED does

not turn orange ensure the Max Speed switch is in the

correct position (usually 60 Hz). It may be necessary to flow

more water and/or temporarily increase the pressure setting

to get the pump speed to 75%. If power is not calibrated,

the controller will use a default value based on the setting of

the motor overload setting dial.
The Dry Well Sensitivity DIP switch determines the

percentage of the power level at which to trigger. Low

Sensitivity uses 75%, High Sensitivity uses 80%.

6: ADVANCED SETTINGS / OPTIONS

Advertising