Table 5: Fault Blink Codes

(continued from previous page)

RED LIGHT CODES (continued)

Flashes

Controller Status

Description

6 Blinks

Ground Fault

This device does not provide personnel protection against

shock. This function is intended for equipment protection

only.

This fault can be caused by:

• Electrical failure of the motor

• Electrical failure of wiring between controller and motor.

• Miswiring of motor cable.

Verify the error by turning power to controller off for 1 minute and then on.

If error persists, motor and wiring between controller and motor must be

checked. Turn power off and wait 5 minutes. See Section 5 Insulation

and Winding Resistance Tests for details.

7 Blinks

Temperature

This fault can be caused by:

• High ambient temperature. The maximum ambient temperature

rating is 122º F (50º C).

• Low ambient temperature. The minimum ambient temperature

rating is 14º F (-10º C).

Check for a fan failure. The fan will turn on when the temperature

inside the controller reaches 140º F (60º C). The fan will turn on for

1 second each time the controller starts the motor. If the fan never

turns on, check fan connections and replace as needed. Ensure that

the external fan intake filter is not blocked or clogged. It can be

removed for cleaning and replacements are available.

8 Blinks

Open Lead

This fault can be caused by:

• Disconnected or broken wire between the controller and motor.

Verify the error by turning power to controller off for 1 minute and

then on. If error persists, motor and wiring between controller and

motor must be checked. Turn power off for 5 minutes. See Section 5

Insulation and Winding Resistance Tests for details.

9 Blinks

Low Pressure Cut-Off

This fault can be caused by:

• Pressure 20 PSI below set point for 30 seconds. May be a broken

pipe or tripped pressure relief valve. If 20 PSI or more pressure

drop for 30 seconds is normal for the system, switch the low pressure

cut-off protection off or change system to prevent the pressure drop.

The controller will automatically

restart when the temperature

reaches an acceptable level. If

fault persists contact installer.

The controller will not restart

if displaying this fault. To clear

the fault, turn off power to the

controller, wait 1 minute, turn

on power to the controller. If

fault persists contact installer.

The controller will not restart

if displaying this fault. To clear

the fault, turn off power to the

controller, wait 1 minute, turn

on power to the controller. If

fault persists contact installer.

The controller will not restart

if displaying this fault. To clear

the fault, turn off power to the

controller, wait 1 minute, turn

on power to the controller. If

fault persists contact installer.