6

The lengths in each of the Wire Sizing tables represent 100% of the allowable voltage drop when motor is running at full

load. When sizing wire, the voltage drop of each wire segment must be included. The total must not exceed 100% of the

allowable drop. Take for example a 1.5 HP 3Ø motor with a distance from Service Entrance to Controller of 100' and 500'

between the Controller and Motor.
• Service Entrance to Controller = 100' of 10 AWG (100/455) = 22 % (455' is from the S.E. to Controller chart)
• Controller to Motor

= 500' of 12 AWG (500/709) = 71 % (709' is from the Controller to Motor chart)

Total Drop (must be ≤ 100%) 93 %

If the distance from the Controller to Motor was 600' (600/709) = 85% + 22% = 107%, we would need to use #10 wire

for that segment, ex. 600/1126 = 53% + 22% (for 100' of #10) = 75% which is acceptable. It is also acceptable to use dif-

ferent wire sizes for the Buried and Well sections of wire.

All Models – Service Entrance to Controller

Controller Motor

Copper Wire Size 75ºC Insulation Exposed to a Maximum of 50ºC (122ºF) Ambient Temperature

Input

HP 14 12 10 8 6 4 3 2 1 1/0

2/0

3/0

4/0

250

300

350

400 500

¾ 279 445 706 1020 1608 2552 3186 4019 5065 6383 8055

1 226 360 571 824 1300 2064 2576 3250 4095 5161 6513 8201

230V 1½ * 286 455 657 1036 1644 2052 2589 3262 4111 5188 6533 8236 9710

1 PH 2 * * 331 478 754 1197 1495 1886 2376 2995 3779 4759 5999 7073 8455 9852

3 * * 246 355 561 890 1111 1401 1766 2225 2808 3536 4458 5256 6283 7321 8343

5 * * * 218

343 545 680 858 1081 1363 1720 2165 2730 3219 3847 4483 5109 6348

3AS20, 30, 50 Controller to Motor – Controllers with 3Ø Motors

Controller Motor

Copper Wire Size 75ºC Insulation Exposed to a Maximum of 50ºC (122ºF) Ambient Temperature

Output

HP 14 12 10 8 6 4 3 2 1 1/0

2/0

3/0

4/0

250

300

350

400 500

¾ 690 1100 1748 2523 3978 6316 7884 9945

1 558 890 1413 2040 3216 5106 6375 8041

230V

1½ 445 709 1126 1625 2562 4068 5078 6406 8072

3 PH

2 324 516 820 1184 1866 2963 3699 4666 5879 7410 9351

3 241 384 609 880 1387 2202 2749 3467 4369 5506 6949 8750

5

* 235 373 539 849 1348 1683 2123 2675 3372 4255 5358 6755 7964 9520

Reduce lengths by 13% for 200 V systems.

* Wire does not meet the N.E.C. ampacity requirement.

Lengths in bold require 90º C wire.

Shading indicates 40º C maximum ambient.

Table 2: Wire Sizing

Maximum Cable Lengths in Feet to Limit Voltage Drop to 5% for 230 V Systems

1AS15 Controller to Motor – Controllers with 2-Wire 1Ø Motors

Motor Lead Lengths - CentriPro 2-Wire Motors -

Based on Service Factor Amps, 30º C Ambient and 5% Voltage Drop

Motor Rating

60º C & 75º C Insulation - AWG Copper Wire Size

Volts

HP kW SFA 14 12 10 8 6 4 2 1/0 2/0 3/0 4/0

½ 0.37 4.7 466 742 1183 1874 2915 4648 7379 11733 14803 18688 23544

230

¾ 0.55 6.4 342 545 869 1376 2141 3413 5419 8617 10871 13724 17290

1

0.75

9.1

241

383

611

968

1506

2400

3811

6060

7646

9652

12160

1½ 1.1 11.0 199 317 505 801 1246 1986 3153 5013 6325 7985 10060

1AS15 Controller to Motor – Controllers with 3-Wire 1Ø Motors

Motor Lead Lengths - CentriPro 3-Wire Motors (CSIR) -

Based on Service Factor Amps, 30º C Ambient and 5% Voltage Drop

Motor Rating

60º C & 75º C Insulation - AWG Copper Wire Size

Volts

HP kW SFA 14 12 10 8 6 4 2 1/0 2/0 3/0 4/0

½ 0.37 6.3 348 553 883 1398 2175 3467 5505 8753 11044 13942 17564

¾ 0.55 8.3 264 420 670 1061 1651 2632 4178 6644 8383 10582 13332

230

1

0.75

9.7

226

359

573

908

1413

2252

3575

5685

7173

9055

11408

1½ 1.1 11.1 197 314 501 793 1234 1968 3124 4968 6268 7913 9969

2 1.5 12.2 180 286 456 722 1123 1790 2843 4520 5703 7199 9070