MANUAL RESET OF DRY WELL FAULT
While setting up and testing the system it is convenient to

have a quick way to clear a Dry Well fault. Pressing both

pushbuttons while the controller has this fault will clear

it and resets the restart time to 1 min. Continuing to hold

the pushbuttons down for an additional 10s will allow the

pump to come up to speed and Dry Well Power Calibration

to occur. The pump is not allowed to stop while any

pushbuttons are held down.

DRY WELL RESTART TIME
After a Dry Well fault occurs, the controller waits a period

of time to allow the well to recover. This period of time can

be chosen to be fixed at 1 minute or increasing in length

with each occurrence of the fault. The factory default is

for restart time to increase each time this fault occurs. The

controller will “forget” one of these faults for every ½ hour

of run time. This allows the restart time to automatically

shrink once a Dry Well condition is resolved. Manually

resetting the fault by pressing both pushbuttons will also

clear the restart time back to 1 minute.

Pushbutton DIP Switch

Direction to

Dry Well Restart Time

to Hold

to Flip

Flip

Down

DIP Switch

Increasing 1/10/20/30/60 min.*

Both Top

Left to Right

Fixed 1 min.

Right to Left

* Factory Default

SIZE OF PRESSURE VARIATION FOR FLOW

DETECTION
The controller uses pressure variation to detect when flow

has stopped. The factory default is for the pressure to vary

+/– 2 PSI. The other choices available are +/– 1 PSI and

+/– 3 PSI. Ideally one would like the smallest pressure

variation while maintaining quick turn off when flow stops.

Too small of a variation may result in the controller not

turning off and/or turning off when it shouldn't. If either

of these problems occur, increasing the pressure variation

should solve the problem. Ensuring the tank has the correct

pre-charge pressure setting and having a spring check valve

on the pump side of the tank and pressure transducer will

provide most reliable turn off performance and allow the

smallest pressure variation setting.

Pushbutton

DIP Switch

Direction to

Pressure Variation

to Hold

to Flip

Flip

Down

DIP Switch

1 PSI

Top

Right to Left

2 PSI*

2nd from Top

Left to Right

3 PSI

Bottom

Left to Right

* Factory Default