Xylem IM229 R06 Aquavar SOLO User Manual

Page 8

Advertising
background image

8

3: INSTALLER PRE-START SELECTIONS
DRIVE SETTINGS AND PROTECTION
Maximum Frequency (Speed) Switch

3AS _ _ Models Only

This switch is only on models no.’s starting with 3AS. It

selects the maximum frequency (motor speed) used to

energize the motor to be either 60 or 80 Hz.
• 60 Hz - Use for matched pump-motor combinations

where the motor HP and pump HP are the same.

Example: 2 HP WE and 2 HP Motor

• 80 Hz - Use for mis-matched pump-motor combinations

where motor HP is larger than the pump HP (typically 2x

larger). Example: 1 HP WE and 2 HP Motor

Pump Stop Sensitivity – 1AS _ _ Model Only

This switch is only on model numbers starting with 1AS.

Selections are High or Low. High will stop the pump

when speed drops to 40Hz. This provides the fastest

turn off when flow stops. If the pump stops when there

is flow in the system, set the Pump Stop Sensitivity to

Low. Low will stop the pump when speed drops to 30Hz.

Low is less likely to cycle but slower turn-off.

Dry Well Sensitivity

Selections are High or Low. This function protects the

system from running dry. The selection depends on

several conditions and pump size.
Start with the sensitivity on high and test by running

pump at various flows. If a dry well fault is triggered,

switch to low setting.
Restart times in minutes are: 1, 10, 20, 30, 60, 60 and

repeating every 60 minutes thereafter.
Example: 1st fault shuts down for 1 minute, next fault

shuts down for 10 minutes, then 20, etc.

Low Pressure Cut-Off

This fault is disabled for the first 10 minutes of pump run

time after power up to allow the system to be purged.
ON Position - Used for constant pressure systems. The

drive will turn off if the system pressure drops 20 PSI

below the system set point pressure for 30 seconds.

This fault must be manually reset, it will not clear

automatically, this may prevent property damage if a pipe

breaks.
OFF Position - Use for open discharge situations such as

filling a pond or tank, or whenever the system pressure

will be 20 PSI or more below the system set point

pressure.

Pressure Drop – 5 PSI or 20 PSI

The pressure drop before the pump restarts can be set to

the standard 5 PSI or to 20 PSI.
The 20 PSI setting results in fewer starts for systems with

leaks. It is recommended for irrigation systems. It will

require a tank pre-charge adjustment. See Tank Sizing and

Tank Pressure Setting.

CURRENT LIMIT PROTECTION
Motor Overload Setting Dial

Failure to properly adjust the Motor

Overload Setting before applying power may

damage the motor or wire and void the warranty.

• Use Tables 3 and 4 to determine which controller and

setting to use. Note that some 200V motors require

upsizing to the next larger controller.

• Set the Motor Overload - Turn the dial pointer to align

with the motor’s service factor amps (SFA). For three

phase motors and any other motor without integral

thermal protection choose the amperage value on the

UIB that is less than or equal to the SFA listed on the

nameplate. For single phase motors and other motors

with integral thermal protection choose the amperage

value on the UIB that is closest to the SFA listed on the

nameplate.

• If the output current exceeds the motor overload setting,

the controller will limit current by reducing the output

voltage and frequency. If the controller reduces the output

frequency to 40 Hz and the current still exceeds the

motor overload setting, the controller will shut down and

indicate Over Current error (4 red blinks).

Purge the System of Air

• Insure that plumbing connections are tight and wire

connections are correct.

• Partially open a valve and turn power to controller on.
• Run the pump and controller with the furthest and

highest faucets or valves in the system open. This will

allow all air to escape the piping system.

• When flow is constant, close the faucets or valves and

allow the system pressure to reach the 50 PSI pre-set

pressure and shutdown.

Controller Status Indicator

(Light Visible Through

Window in Cover)

The controller status indicator light has 3 possible modes:
• Solid green = Standby, pump not running. There is no

water flow or the SWITCH INPUT is open.

• Blinking green = Pump running. There is flow (possibly a

leak) and the SWITCH INPUT terminals are connected to

each other (closed).

• Red = Error/Fault. Light will blink to indicate a particular

fault. See Troubleshooting Section for Fault Codes.

PRESSURE ADJUSTMENT – Only if pressure

other than 50 PSI is desired:

• Adjust tank pressure according to the desired set pressure

- see Tank Sizing and Tank Pressure Setting section.

• Open a faucet and allow pump to start and purge the

system of air.

• When pressure gauge reaches 50, Press and Hold the

Increase or the Decrease pushbutton until the desired

pressure shows on the gauge.

• The larger the tank the longer it will take to increase

pressure.

• When desired pressure is reached, close the faucet and

allow the system to shut down.

Pump size determines the maximum flow and head which can

be provided, if flow or head are not sufficient and rotation on

three-phase units has been verified, a larger pump is required.

3. INSTALLER PRE-START SELECTIONS

WARNING

Advertising