Opening controller cover, Mounting controller, Pump and piping – Xylem IM229 R06 Aquavar SOLO User Manual

Page 4: Check valve, For a 5 psi pressure drop set-up, For a 20 psi pressure drop set-up, Splicing drop cable to motor leads, Wiring pressure transducer

Advertising
background image

4

Opening Controller Cover

Lay the controller on a flat surface or hang

on wall before removing the cover screw.

Failure to do so may result in dropping and damaging the

unit. Once screw is removed, lift the cover up and out to

remove. There is a locking tab on the bottom of the unit to

accommodate a padlock if so desired.

Mounting Controller

Three screws are provided for mounting the enclosure.
Using the enclosure as a guide, select a mounting location.

First install the top screw in the mounting surface leaving

the head of the screw approximately

1

8

" from the surface.

Hang the enclosure on this screw. Finish by installing the

two bottom screws and tightening the top screw. Be sure

to leave a minimum of 6" of clearance on each side of the

controller to ensure proper cooling.

Pump and Piping

Do not install any valves (except check

valves), flow control devices or filters

between the pressure transducer and the pump. It is

allowable to run branches off the pipe between the pump

and transducer as long as no flow restricting devices are

between the pump and transducer.
NOTICE: The terms Transducer and Pressure Sensor are

equal and interchangeable.

EXPLODING TANK CAN INJURE OR

KILL.

Always protect the tank from over pressure by installing

a pressure relief valve large enough to limit the system

pressure below the maximum working pressure of the tank.

Install the tank at a point in the system where the maximum

possible system pressure cannot exceed the maximum

working pressure of the tank. Install the pressure relief valve

at the tank.

Avoid property damage caused by pressure

relief valve opening. Pipe the pressure relief

valve discharge to a drain or other location so that property

damage and flooding will not occur.

Locate the tank and transducer where they

will not freeze.

Ensure the system pressure setting does not exceed the

maximum working pressure of the tank.
For optimum performance, as a minimum, we recommend

using the same size pipe as the pump discharge between the

pump and the tank. Smaller diameter pipe may severely limit

the maximum capacity of the system. On long runs, larger

pipe may be beneficial for optimum performance and flow.

If using a torque arrestor, install it on the

discharge pipe before connecting pipe to

the discharge head.

Check Valve

Use a spring check valve between pump and tank for

reliable turn-off when flow stops.

TANK SIZING AND TANK PRESSURE SETTING -

Refer to Table 1 for recommended tank size. On pre-existing

systems, larger tanks may be used.

Table 1: Systems with Small Tanks

Pump Size

Minimum Tank

GPM

Total Volume

5 - 6

2

7 - 8

2

10 -12

2

13 -15

4

18 - 20

4

25 - 28

5

33 - 35

7

40 - 45

9

55 - 60

12

75 - 80

15

For a 5 PSI Pressure Drop Set-up:

Set the tank pressure, while tank is empty of water, to 20 psi

below the desired system pressure setting. Ex. for a 50 psi

system pressure, charge the tank to 30 psi. *

For a 20 PSI Pressure Drop Set-up:

Set the tank pre-charge to 30 psi below the desired system

pressure setting. Ex. for a 50 psi system pressure, charge the

tank to 20 psi. *

* The tank pre-charge is always checked with the tank empty of water.

Splicing Drop Cable To Motor Leads

The underwater connection where the drop cable connects

to the motor wires must be done using a waterproof heat

shrink kit. To make the connection, first strip the wires

½" and place the heat shrink tubes over the wires. Then,

connect the wires using the crimps. Finish by shrinking the

tubes over the crimps heating from the center outward.

The sealant in the tube will flow out the ends making a

watertight seal. If a heat shrink tube is burnt or split, the

connection will need to be remade.

Vinyl electrical tape is not acceptable for

underwater splices when using variable

speed drives due to the high potential for leakage to ground

through taped joints. Failure to use a waterproof heat shrink

kit will void the warranty.
Before installing the motor in the well, the drop cable must be

connected to the motor wires. Refer to the wire size chart when

selecting wire size for the drop cable. See Wire Sizing Table.

Wiring Pressure Transducer

Transducer wires must never be in same

conduit with power wires. There should

always be a minimum of 12" between transducer wires

and power wires. Failure to separate these wires can cause

controller malfunctions.
The pressure transducer cable is pre-wired at the factory. If

desired, the length of the cable can be changed. The cable

can also be put in conduit to protect against damage.
To change the length of the transducer cable:
• Cable length cannot exceed 200'.
• Disconnect transducer wires from terminal block by

pushing down on tabs at rear of block one at a time and

pulling the wires out of the terminal.

• Splice additional cable to transducer wire, cut off excess as

required.

WARNING

CAUTION

CAUTION

WARNING

CAUTION

CAUTION

CAUTION

CAUTION

Advertising