Xylem IM229 R06 Aquavar SOLO User Manual

Page 5

Advertising
background image

5

• Reconnect wires to terminal block. Be sure wire colors

match labels on circuit board (B = Black, R = Red, W =

White).

To put the transducer cable in conduit, do the following:

Disconnect the cable from the terminal block and remove

the cable strain relief in the bottom of the enclosure.

Starting at the enclosure, run flexible or rigid ½" conduit to

where the transducer is located. The last few feet of conduit

adjacent to the transducer will need to be flexible. The

conduit must be well supported – NO stress can be placed

on the pressure transducer connector. Use a strain relief

bushing to seal around the pressure transducer connector.

After reconnecting the transducer wires to

the terminal block and ground terminal, tug

on each wire individually to ensure they are tight.

Any exposed metal in the system piping,

including transducer case, must be grounded

to the service entrance per NFPA 70: National Electrical

Code, Article 250.
The transducer cable has a Green ground wire and a ground

clamp supplied to facilitate grounding the transducer. See

Figure 1.

Motor Wires – See Table 2

NOTE: A MINIMUM OF 75ºC COPPER WIRE IS

MANDATORY.
Refer to the Table 2 for wire sizing and maximum wire

lengths. Charts are designed to limit voltage drop to 5%.
Insure that the wire is rated for direct burial and/or

submergence.
Figure 2 shows the terminal block where the motor and

input wires connect. The circuit board near the terminal

block is labeled to show where to connect the motor wires.

For all motors, the green wire from the motor must be

attached to the terminal labeled GND.
For 2-wire, 1Ø motors with 2 black wires, connect one

black wire to each of the terminals labeled BLK and leave

the terminal labeled X empty. It doesn't matter which black

wire goes to which BLK terminal.
For 3Ø or 3-wire, 1Ø motors with red, black and yellow

wires, connect the red wire to RED, black wire to BLK and

yellow wire to YEL.

Input Power

SHOCK OR ELECTROCUTION

HAZARD

Connect a ground wire from the service panel to the

terminal marked GND. Controller has high leakage to

ground. Controller ground terminal must be connected to

the service entrance ground terminal. Failure to do so will

result in high voltage being present on the controller chassis.

Connect two “hot” wires from the 2 pole circuit breaker to

the terminals marked L1 and L2.
The input power system used must be a grounded power

system. The voltage measured from L1 to L2 must be in the

range of 196Vac to 265Vac. The voltage measured from

L1 to GND must be equal to the voltage measured from

L2 to GND. These voltages must be within the range of

120Vac +/- 10%. Reduced input voltage will reduce system

performance.
Do not use a Ground Fault Circuit Interrupter (GFCI) with

this product or nuisance tripping will result.

Input Power and Motor Lead Connections

Figure 2: Wiring Connections

CAUTION

CAUTION

L1 L2 GND

GND RED BLK YEL

Incoming Power

Wires to Motor

1AS15

3AS_ _

Figure 1: Transducer Grounding

DANGER

1Ø – 2W/3W

Advertising