32



Manual Mode

Manual Mode

Manual Mode

Manual Mode
In Manual mode the pumps may be started and stopped with the P1/ON-OFF, P2/ON-OFF, P3/ON-OFF
keys and there is no pressure regulation.
The controls for minimum pressure switch, minimum level alarm, maximum pressure threshold alarm,
minimum pressure threshold alarm, alarm block from outside, are deactivated.

Automatic Mode

Automatic Mode

Automatic Mode

Automatic Mode
In automatic mode the pumps are controlled by the SM30 BSETF3 board according to the demand
received from the pressure sensor or from the pressure switch consent, to keep the pressure at the
desired level.
In order to operate correctly, the board must be programmed with the system parameters.
Whenever the board is switched on, the default mode is automatic.

Programming

Programming

Programming

Programming
The board is programmed by modifying the parameters in two menus, the Parameters Menu and the
Service Menu.
A third menu allows the display of the alarms that have occurred. The Alarms Log menu is accessible in
both automatic and manual mode.

Parameters menu

Parameters menu

Parameters menu

Parameters menu
The SM30 BSETF3 electronic board is supplied already programmed, however it may be necessary
to modify some parameters for better operation. The Parameters programming menu contains the
system parameters (number of pumps, presence of jockey pump, choice between system with
pressure sensor and system with pressure switches, default, complete list see chapter 6).


Service menu

Service menu

Service menu

Service menu
In this menu it is possible to change the language and enable changing of the following
parameters in automatic operation: pump START/STOP working thresholds, probe sensitivity,
timing, compensation of leaks.

Symbol

Name

Description

↑UP/SU

Switch between Automatic and Manual mode
Scroll windows up
Increase by one value during “edit data”

↓DOWN /GIU’

Scroll windows down
Decrease by one value during “edit data”

OK/MENU’

Confirm menu
Confirm data inserted

P1, P2, P3

Manual mode, start (ON) and stop (OFF) pump “n”.
The P3 key also has the (EXIT) function and
acknowledges/switches off the FAULT led

Advertising