9 FIELD BUS

9 FIELD BUS

9 FIELD BUS

9 FIELD BUS
List of the main available Modbus R (Read) and R/W (Read/Write) parameters

ADDRESS

DESCRIPTION

RANGE

DEFAULT

40003

ANALOG OUTPUT value

R

40004

AN. INPUT AI1 value

R

40005

AN. INPUT AI2 value

R

40021

DIGITAL INPUT status

R

40032

P1 STOP THRESHOLD

R/W

350

40033

P1 START THRESHOLD

R/W

270

40034

P2 STOP THRESHOLD

R/W

340

40035

P2 START THRESHOLD

R/W

260

40036

P3 STOP THRESHOLD

R/W

330

40037

P3 START THRESHOLD

R/W

250

40041

P1 START DELAY

R/W

003

40043

P2-3 START DELAY

R/W

005

40044

P1 STOP DELAY

R/W

005

40045

P2-3 STOP DELAY

R/W

003

40121

DAY (AUTOTEST)

R/W 0=Monday, 1=Tuesday,
2=Wednesday, 3=Thursday, 4=Friday,
5=Saturday, 6=Sunday

0

40122

HOUR (AUTOTEST)

R/W

10

40123

MINUTES (AUTOTEST)

R/W

00

40124

NIGHT/DAY FUNCTION

R/W 0=disabled, 1=by int. clock,
2=by ext. control, 3=by int. and ext.
control

0

40125

NIGHT/DAY VALUE

R/W

100

40126

N/D START HOUR

R/W

40127

N/D START MINUTES

R/W

40128

N/D END HOUR

R/W

40129

N/D END MINUTES

R/W

40130

RS485 MODBUS ENABLE

R/W 0= disabled, 1=enabled

1

40131

MODBUS ADDRESS

R/W

40132

PARITY

R/W 0=none, 1=even, 2= odd

0

40133

DELAY

R/W

40134

BAUD RATE

R/W 0=1200, 1=2400, 2=4800,
3=6900, 4=19200, 5=38400,
6=57600, 7=115200

5

40135

P1 OPERAT.HOURS

R

40136

P2 OPERAT.HOURS

R

40137

P3 OPERAT.HOURS

R

40138

ALARMS LOG: type 1

st

trip

R 0=flash init. error, 1=f.ram
init.error, 2= LOW WATER alarm, 3=
SENSOR 1 alarm, 4= SENSOR 2 alarm,
5=OVERLOAD 1, 6=OVERLOAD 2, 7=
OVERLOAD 3, 8= AUTOTEST FAIL P1,
9=AUTOTEST FAIL P2, 10= AUTOTEST
FAIL P3, 11=CONVEYOR LIMIT,
12=HIGH PRESSURE,
13=MAX.PRES.THRESH. alarm,
14=MIN.PRES.THRESH. alarm