9 BUS DE TERRAIN

9 BUS DE TERRAIN

9 BUS DE TERRAIN

9 BUS DE TERRAIN
Liste des principaux paramètres R (Lecture) et R/W (Lecture/Écriture) disponibles par Modbus.

ADRESSE

DESCRIPTION

CHAMP

DÉFAUT

40003

Valeur SORTIE ANALOGIQUE

R

40004

Valeur ENTRÉE AN. AI1

R

40005

Valeur ENTRÉE AN. AI2

R

40021

État ENTRÉES NUMÉRIQUES

R

40032

SEUIL ARRÊT P1

R/W

350

40033

SEUIL DÉMAR. P1

R/W

270

40034

SEUIL ARRÊT P2

R/W

340

40035

SEUIL DÉMAR. P2

R/W

260

40036

SEUIL ARRÊT P3

R/W

330

40037

SEUIL DÉMAR. P3

R/W

250

40041

RET. DÉM. P1

R/W

003

40043

RET. DÉM. P2-P3

R/W

005

40044

RET. ARRÊT P1

R/W

005

40045

RET. ARRÊT P2-P3

R/W

003

40121

JOUR (AUTOTEST)

R/W 0=Lundi, 1=Mardi, 2=Mercredi,
3=Jeudi, 4=Vendredi, 5=Samedi,
6=Dimanche

0

40122

HEURE (AUTOTEST)

R/W

10

40123

MINUTES (AUTOTEST)

R/W

00

40124

FONCT. NUIT/JOUR

R/W 0=désactivé, 1=dps horloge int.,
2=dps commande ext., 3=dps
commande int. et ext.

0

40125

VALEUR NUIT/JOUR

R/W

100

40126

HEURE DÉP. N/J

R/W

40127

MINUTES DÉP. N/J

R/W

40128

HEURE FIN N/J

R/W

40129

MINUTES FIN N/J

R/W

40130

RS485 MODBUS ACTIVÉ

R/W 0= désactivé, 1=activé

1

40131

MODBUS ADRESSE

R/W

40132

PARITÉ

R/W 0=sans, 1=pair, 2= impair

0

40133

RETARD RÉPONSE

R/W

40134

BAUD RATE

R/W 0=1200, 1=2400, 2=4800,
3=6900, 4=19200, 5=38400,
6=57600, 7=115200

5

40135

CMPT HORAIRE P1

R

40136

CMPT HORAIRE P2

R

40137

CMPT HORAIRE P3

R

40138

REG. ALARMES : type 1

ère

interv.

R 0=erreur flash, 1=erreur ferroram,
2= al. MANQUE d’EAU, 3= al.
CAPTEUR 1, 4= al. CAPTEUR 2, 5=al.
THERMIQUE 1, 6=al. THERMIQUE 2,
7= al. THERMIQUE 3, 8= al. A-TEST
ÉCHOUÉ P1, 9=al. A-TEST ÉCHOUÉ P2,
10= al. A-TEST ÉCHOUÉ P3, 11=al.
H.C., 12=al. HAUTE PRES., 13=al.
SEUIL PRESS. MAX SEUIL PRESS. MIN

40139

REG. ALARMES : date 1

ère

interv.

R