6.2.18 HOUR COUNTER

6.2.18 HOUR COUNTER

6.2.18 HOUR COUNTER

6.2.18 HOUR COUNTER

Phase

Display

Comment

Field

Default

0

0

0

0 HOUR COUNTER

HOUR COUNTER

HOUR COUNTER

HOUR COUNTER

1

P1 OPERAT.HOURS

Reads pump 1 operating hours

0

2

P2 OPERAT.HOURS

Reads pump 2 operating hours

0

3

P3 OPERAT.HOURS

Reads pump 3 operating hours

0

4

OP.HOURS RESET

Resets memory of pump hour counter





7 ALARMS

7 ALARMS

7 ALARMS

7 ALARMS
In MANUAL and AUTOMATIC mode the Alarms Log can be displayed by pressing the

↑UP and OK/MENU

buttons.
All the alarms are indicated and stored in the memory, but some block only automatic operation of the
set.
All the alarms cause the lighting of the red FAULT led.
The alarm for low water level on intake lights the red LOW WATER led.

Alarm display

Alarm display

Alarm display

Alarm display
The last ten alarms that occurred are stored in the board and are visible on the alarms log menu.
If an alarm occurs, the FAULT led lights up and the alarm is stored in the memory.
The alarm is shown on the display for the whole time in which the condition remains.
When the condition ceases, the alarm is automatically reset, while the blinking FAULT led remains lit.

The alarm can be acknowledged with the button P3 (EXIT): the FAULT led is turned off.

Resetting of the alarms log is done in manual mode in the Alarms menu.

ALARMS LOG MENU

ALARMS LOG MENU

ALARMS LOG MENU

ALARMS LOG MENU

Phase

Display

Comment

0

Alarm Message 1:

Date & time

Most recent alarm

1

Alarm Message 2:

Date & time

Alarm

2

Alarm Message 3:

Date & time

Alarm

3

Alarm Message 4:

Date & time

Oldest alarm

LIST OF AL

LIST OF AL

LIST OF AL

LIST OF ALARMS

ARMS

ARMS

ARMS

ALARMS LOG

Definition

Comment

MAX.PRES.THRESH.

MAXIMUM PRESSURE
ALARM
(by sensor)

Exceeding of set maximum pressure threshold for a
time greater than the defined delay.
It is active only in the mode with pressure sensor and is
excluded in manual operating mode.
If the alarm is activated for three consecutive times at
intervals of one minute, the board inhibits the
automatic operation; a manual reset is required.

INFORMATION FOR THE INSTALLER AND USER