Phase

Display

Comment

Field

Default

0

0

0

0 ALARM RELAY

ALARM RELAY

ALARM RELAY

ALARM RELAY

1

DELAY ON RELAY

Delay in seconds of alarm relay
activation

0..60 s

0 s

2

DELAY OFF RELAY

Delay in seconds of alarm relay
deactivation

0..60 s

0 s

3

LOGIC RELAY

Active: for event =ON
The contact is open in case of event
Passive: for event =OFF
The contact is closed in case of event

ACTIVE
PASSIVE

PASSIVE

4

DISABLE RELAY

Automatic when the alarm ceases or
manually with button P3 (EXIT)

AUTOMATIC
MANUAL

AUTOMATIC

5

RELAY ON O.L.

PUMP OVERLOAD ALARM
Activates alarm relay for tripping of an
overload/ptc of any active pump.

YES
NO

YES

6

RELAY ON L.O.W.

LOW WATER ALARM
Activates alarm relay for low
level/pressure on intake through
probes/float/min. pressure switch

YES
NO

YES

7

RELAY ON SENSOR

SENSOR ALARM
Activates relay for fault in activated
sensors.

YES
NO

YES

8

RELAY ON C.LIMIT

CONVEYOR LIMIT
Activates relay for Minimum Pressure
Switch alarm (connected to digital
input AUX3, to be set as
CONV.L.SWITCH)

YES
NO

NO

9

RELAY ON EXT.AL.

EXTERNAL FAULT ALARM
Activates relay for external fault arriving
from digital input AUX2.

YES
NO

NO

10

RELAY ON MAX P.

MAX PRESSURE ALARM
Activates relay for maximum pressure
alarm arriving from digital input AUX1
or from MAX.PRES.THRESH.

YES
NO

NO

11

RELAY ON MIN P.

MINIMUM THRESHOLD ALARM
Activates relay for minimum pressure
threshold alarm.

YES
NO

NO


6.2.8 PROGRAMMING THE ALARMS

6.2.8 PROGRAMMING THE ALARMS

6.2.8 PROGRAMMING THE ALARMS

6.2.8 PROGRAMMING THE ALARMS

Phase

Display

Comment

Field

Default

0

0

0

0 ALARMS

ALARMS

ALARMS

ALARMS

1

MIN.PRES.THRES
H.

MINIMUM PRESSURE ALARM
Function available only with systems with a
pressure sensor.
Set the minimum pressure value below
which the system interrupts pump
operation.

The system control is performed only if at
least one pump is active.

To disable, insert pressure = 0 bar

0..FS bar

0 bar