Xylem Fixed speed booster sets programming manual/Electronic control board SM30 User Manual

Page 41

Advertising
background image

en

en

en

en

41

6.2.4 TIMING

6.2.4 TIMING

6.2.4 TIMING

6.2.4 TIMING
Timing is active both with systems with pressure switches and with systems with sensors.

Phase

Display

Comment

Field

Default

0

0

0

0 TIMING

TIMING

TIMING

TIMING

1

P1 START DELAY

Delay in starting P1 (jockey included).
The time count begins from the start
request from the pressure switch/sensor.

0..100 s

3 s

2

P2-3 START DELAY

Delay in starting P2 - P3. The time count
begins from the start request from the
pressure switch/sensor.

0..100 s

5 s

3

P1 STOP DELAY

Delay in stopping P1 (jockey included).

The time count begins from the stop
request from the pressure switch/sensor.

0..100 s

5 s

4

P2-3 STOP DELAY

Delay in stopping pumps P2 - P3. The
time begins from the stop request from
the pressure switch/sensor.

0..100 s

3 s

5

DYNAMIC TIMES

Settable only on system with sensor.
Halves the times previously set in the
case of excessive variation of the
pressure/level/etc. of the system.

YES
NO

NO



6.2.5 PERIODIC AUTO TEST

6.2.5 PERIODIC AUTO TEST

6.2.5 PERIODIC AUTO TEST

6.2.5 PERIODIC AUTO TEST----RUN

RUN

RUN

RUN

In systems subject to long periods of inactivity it is recommended to perform a periodic automatic test
(auto test-run) with the aim of checking the performances of the group.

In any case the autotest cannot replace programmed maintenance, which must be carried out
periodically. A weekly interval is recommended.

To start the test request the board’s internal clock may be used, or an external command. When autotest
is enabled, the alarm relay is automatically configured to control the solenoid valve.

It is also necessary to ensure that the parameter CONFIG. IN. AUX3 in the DIGITAL IN/OUT MENU is set as
CONV.L.SWITCH (Minimun Pressure Switch).

Phase

Display

Comment

Field

Default

0

0

0

0 AUTO

AUTO

AUTO

AUTO----TEST

TEST

TEST

TEST RUN

RUN

RUN

RUN

1

AUTO TEST REQ.

Autotest command source.

The possible settings are:
Disabled: autotest is inhibited.

Internal clock: autotest is activated on
the day and time requested from the
SM30 BSETF3 board by the internal
clock.

Ext. command: autotest is activated by
the external command connected to the
digital input AUX1

DISABLED
INTERNAL
CLOCK

EXT.ON /OFF

DISABLED

Advertising