Xylem Fixed speed booster sets programming manual/Electronic control board SM30 User Manual

Page 47

Advertising
background image

en

en

en

en

47

3

AI1 FILTER

Software filter (no. samples) of the
analog input AI1 signal

1..199

1

4

AI1 UNIT

Setting the unit of measurement on
input AI1

DISABLED
bar
°C

m³/h
m

bar

5

AI2 SENSOR TYPE

Type of transducer connected to the
analog input AI2 (if selected on System)

4-20 mA
0-20 mA
0-10 V
0-2 V

4-20 mA

6

ZERO ADJUST AI2

Visible only if 4-20mA selected.
Acquisition of input zero 4 4-20 mA
Adjustment is possible only in the range
3.5… 4.5mA
If adjustment has a positive result the
message SENSOR ADJUST OK appears
If out of range the message SENSOR
ADJUST KO appears

YES
NO

NO

7

AI2 FILTER

Software filter (no. samples) of the
analog input AI2 signal

1..199

1

8

AI2 UNIT

Setting the unit of measurement on
input AI2

DISABLED
bar
°C

m³/h
m

bar

9

ANALOG OUTPUT

Function that can be attributed to analog
output Out_A

DISABLED
AI1
AI2

DISABLED

10

AN.OUT1 TYPE

Full scale analog output AO1

4-20 mA
0-20 mA
0-10 V
0-2 V

4-20 mA


6.2.11 PROGRAMMING DIGITAL INPUTS / OUTPUTS

6.2.11 PROGRAMMING DIGITAL INPUTS / OUTPUTS

6.2.11 PROGRAMMING DIGITAL INPUTS / OUTPUTS

6.2.11 PROGRAMMING DIGITAL INPUTS / OUTPUTS

Phase

Display

Comment

Field

Default

0

0

0

0 DIGITAL IN / OUT

DIGITAL IN / OUT

DIGITAL IN / OUT

DIGITAL IN / OUT

1

PR.SW.1 LOGIC

Terminal 2 only if pressure switch
operation enabled.

NC / NO

NC

2

PR.SW.2 LOG

Terminal 3 only if pressure switch
operation enabled.

NC / NO

NC

3

PR.SW.3 LOGIC

Terminal 4 only if pressure switch
operation enabled.

NC / NO

NC

4

CONFIG. AUX1 IN.

Configuration of input AUX1 as max.
pressure pressure-switch or external
auto-test command.

DISABLED
HIGH
PRESSURE
START
AUTOTEST

DISABLED

5

CONFIG. AUX2 IN.

Configuration of input AUX2 as external
consent (NO) or external alarm (NC).

DISABLED
EXT.ALARM
EXT.ON/OFF

DISABLED