2

DAY

Setting of the day autotest is to be
performed (parameter active only if the
command source is set as INTERNAL
CLOCK)

MON
..SUN

MONDAY

3

HOUR

Setting of the hour when autotest is to
be performed (parameter active only if
the command source is set as INTERNAL
CLOCK)

0..24 h

10

4

MINUTES

Setting of the minutes when autotest is
to be performed (parameter active only if
the command source is set as INTERNAL
CLOCK)

0..60 min

00


How to st

How to st

How to st

How to start autotest

art autotest

art autotest

art autotest

The periodic autotest is activated by:

-

an external command, connected to the digital input AUX1

or
-

the board internal clock

If the request arrives during operation of the pumps, autotest will be put in standby and this message
will appear at regular intervals:

AUTO

AUTOTEST PENDING


As soon as the set has all the pumps off, autotest will start with the following message

AUTOTEST P1

AI1 +###.## bar


During the pause between testing one pump and the other the following message appears:


AUTOTEST STAND

AI1 +###.## bar


If the autotest has had a negative result the following message appears:

AUTO

AUTOTEST FAIL P#

Autotest execution phases

Autotest execution phases

Autotest execution phases

Autotest execution phases
The test is composed of the sequences:
a) Receiving the command.

b) Opening the solenoid valve on the set by the control of the SOLENOID VALVE relay.
c) Starting the first pump.
d) Closing the solenoid valve.
e) Stopping the pump being tested after two minutes.
f) Waiting one minute.
g) Performing test on next pump.