0 data management, 1 scte-hms configurable alarms, continued – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual

Page 53

Advertising
background image

53

745-814-B11-001, Rev. C (03/2014)

6.0 Data Management

Discrete Alarms

Description

Setting

psInverterStatus (1)

Inverter OFF

Disable

psInverterStatus (2)

Inverter running due to loss of AC Line voltage

discreteMinor

psInverterStatus (3)

Self Test initiated locally

Disable

psInverterStatus (4)

Self Test initiated remotely

Disable

psInverterStatus (5)

Last Self Test failed

Disable

psMajorAlarm (1)

No Alarm

Disable

psMajorAlarm (2)

Alarm

discreteMajor

psMinorAlarm (1)

No Alarm

Disable

psMinorAlarm (2)

Alarm

discreteMinor

psTamper (1)

Closed

Disable

psTamper (2)

Open

discreteMajor

psInputVoltagePresence (1)

AC Line Voltage lost

Disable

psInputVoltagePresence (2)

AC Line Voltage present

Disable

Battery Standby Time Remaining

(1)

Over 3 hours remaining

Disable

Battery Standby Time Remaining

(2)

2 to 3 hours remaining

Disable

Battery Standby Time Remaining

(3)

1 to 2 hours remaining

discreteMinor

Battery Standby Time Remaining

(4)

Less than 1 hour remaining

discreteMajor

Battery Standby Time Remaining

(5)

Calculating

Disable

Battery Standby Time Remaining

(6)

Not Available

Disable

tibControlMode (2)

Device is under local control

Disable

tibControlMode (3)

Remote device is not responding

discreteMajor

Discrete Alarms for Optional Generator
genGeneratorStatus (1)

Generator OFF

Disable

genGeneratorStatus (2)

Generator running (Test)

discreteMinor

genGeneratorStatus (3)

Generator running

discreteMajor

genGeneratorStatus (4)

Generator fail

discreteMajor

genGasHazard (1)

No Alarm

Disable

genGasHazard (2)

The concentration of hydrocarbon fuel in the generator enclosure has exceeded safe limits. Generator

operation is suspended. The alarm is cleared when the sensor reports safe conditions, and the alarm is reset

via the resetLatchedAlarms(3) command found in the genEquipmentControl MIB point.

discreteMajor

genWaterIntrusion (1)

No Alarm

Disable

genWaterIntrusion (2)

Water level within the generator or fuel enclosure has exceeded safe limits for generator operation. Generator

operation is suspended while this alarm is active. The alarm resets when the water returns to a safe level.

discreteMajor

genPadShear (1)

No Alarm

Disable

genPadShear (2)

Indicates that the generator or fuel enclosure has shifted from its mounting position. Generator operation is

suspended. The alarm resets when the unit is returned to its original position.

discreteMajor

genEnclosureDoor (1)

No Alarm

Disable

genEnclosureDoor (2)

Generator and/or auxiliary fuel enclosure door is open

discreteMajor

genCharger (1)

No Alarm

Disable

genCharger (2)

Ignition battery charger is not operating correctly

discreteMajor

genFuel (1)

No Alarm

Disable

genFuel (2)

Indicates the engine's fuel supply is insufficient for extended operation. Alarm resets when fuel is replenished. discreteMajor

genOil (1)

No Alarm

Disable

genOil (2)

Indicates the engine's oil is inadequate for safe operation. Alarm resets when the condition returns to normal.

discreteMajor

genMinorAlarm (1)

No Alarm

Disable

6.2.1 SCTE-HMS Configurable Alarms, continued

Table 6-4, Recommended Settings for Discrete Alarms