4 battery alarms, 0 data management – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual

Page 60

Advertising
background image

60

745-814-B11-001, Rev. C (03/2014)

Table 6-9, Battery Alarms: Classifications, Causes and Corrections

6.2.4 Battery Alarms

The Intelligent CableUPS detects a wide array of battery alarms and displays the type of active

alarm in the Smart Display screen and the severity of alarm (e.g., Major/Minor) by means of the

Inverter Module LEDs.

6.0 Data Management

NOTE:

The cause of a psMajor or psMinor alarm can be determined by checking the Discretes table in the Alpha MIB

or by viewing the Web page. The cause will have the value of

ALARM.

Active Alarm

Alarm

type

Alarm

Category

Probable Cause of Alarm

Corrective action

Standby

Disabled

NO BATTERIES

Major

BATT

Detected the absence of batteries (alarm inactive when

battery capacity or number of battery strings is set to 0)

1. Check Batt Breaker

2. Check Connections

3. Check Battery Fuse

YES

LOW BATT VOLTS

Major

BATT

Battery voltages below 1.833V/cell

1. Check AC Input

2. Restore AC Input

3. Connect Generator

NO

HIGH BATT VOLTS

Major

BATT

Battery voltages above 4.5V over target charger voltage

1. Check Batteries

2. Replace Inverter

NO

BATTERY EOD

Major

BATT

Batteries dropped below the low voltage shutdown level

(low battery disconnect)

1. Restore AC Input

2. Connect Generator

YES

BATTERY FAIL

Major

BATT

Charge current > 5.0A for 7 days while in float mode

1. Check Batteries

2. Replace Batteries

NO

BATT TEMP PROBE

Minor

BATT

Precision Temperature Sensor (PTS) failed or is not

installed.

1. Check Connection

2. Replace Sensor

NO

REFRESH/BATT REFRESH ALARM

Minor

BATT

Battery Temperature Exceeded 60°C

1. Check Charger Settings

2. Check Batteries

3. Check Battery Temperature

NO

SAG OPTION

Minor

BATT

I2C has failed between XM3 and SAG

1. Check Ribbon Cable

2. Replace SAG

NO

SAG DELTA MEAN

Minor

BATT

Battery voltage is either too high or low from mean

1. Check Batteries

2. Replace Batteries

NO

SAG RELAY STUCK

Minor

BATT

Relay has stuck or 36V or 0V wire is no longer

connected

1. Check SAG Wires BAT

2. Check SAG Wires Unit

3. Replace SAG Wires

NO

STR X MISWIRED

Minor

BATT

Battery wires are not connected properly

1. Check SAG Wires BAT

2. Check SAG Wires Unit

3. Replace SAG Wires

NO

SAG NOT CALIBRAT

Minor

BATT

Calibration data is not or is no longer available

1. Replace SAG

NO

X BAL STAGE

Minor

BATT

Stage 0 and 1 are normal. Stage 2 shows that the

batteries are not of similar capacity. Stage 3-5 trigger

check battery alarm to show that there is a major

capacity imbalance

1. Check Batteries

2. Replace Batteries

NO

SAG NO HARNESS

Minor

BATT

Battery wires are not connected properly

1. Check SAG Wires BAT

2. Check SAG Wires Unit

3. Replace SAG Wires

NO